6.3.3 Test Menu Overview '

The test menu is used to test the detector gas
reading using bump test gas, and for simulation of
alarm and fault display and output operation. The
test menu also contains the detector Inhibit facility.
Use the 's' up and 't' down buttons to select either
bump test or alarm/fault test. Press the '3' accept
button to enter that submenu.
The table below shows an overview of the
test submenus and how they are navigated.
For a detailed step-by-step instruction of how to test
the detector operation refer to Section 7.2.
Note
In bump test mode, the Modbus/TCP outputs
are not inhibited. Only the 4-20mA and alarm
outputs are inhibited.
The bump gas test is a functional check only.
Consult local guidelines for recommended
best practices. Bump test concentrations
recommended in Appendix B are calculated
to generate a minimum first alarm level
response.
tESt'
Display
Bump
bUmP
Alarm/
fault
SIm
Inhibit
Inh
4-20 mA
4-20
mA
6-10
Midas
Gas Detector
®
Table 6-5. Test Submenu
Screen 1
Screen 2
Apply bump
Press 'X' to
test gas and
exit to test
display shows
menu
measured gas
concentration
with all alarm
outputs
inhibited
Display shows
Display
'Sim' and
shows
flashes 'SIm'
's'
'SuRE'.
and simulates
the A1
the selected
symbol.
4 states:
Fault display
s: alm 1
: alm 2
flashing:
inst flt
: maint flt
Press s or t
Set inhibit
to select ALm,
timeout
displayed and
ALm-Ft, ALL
period
or nonE inhibit
state
inhibit state.
Display shows
'S XX' where
XX is the mA
value
Press s or t
for the desired
mA output
Screen 3
Screen 4
Display
Press 'X'
to exit
and select
another
A1, A2 or
simulation or
'X' again to
and output.
return to test
submenu
UPdt is
unit enters
selected
Display
returns to
submenu