Properties
1.1 2AI U HS analog electronic module (6ES7134-4FB51-0AB0)
•
Crosstalk between the inputs
Operational limit
(in the entire temperature range, with reference to
the input range)
Basic error limit (operational limit at 25°C with
reference to input range)
Temperature error (with reference to the input
range)
Linearity error (with reference to the input range)
Repeatability
(in steady state at 25°C with reference to input
range)
Input ranges (rated value)/input resistance
•
Maximum input voltage for voltage input
(destruction limit)
Connection of the sensors
•
Smoothing of the measured values
DPV1 only
1
Parameter assignment error
2
Violation of lower limit value
Violation of upper limit value
Open circuit (only with 1 V to 5 V)
Process interrupt lost
10
Common mode interference (U
Voltage
For measuring voltage
Suppression of interference, limits of error
) < 100 VSS) > 70 dB
cm
> 50 dB
± 0,3 %
± 0,2 %
±0,01 %/K
± 0,01 %
± 0,05 %
Data for selecting a sensor
± 10 V/min. 100 kΩ
± 5 V/min. 100 kΩ
± 2.5 V/min. 100 kΩ
1 V - 5 V/min. 100 kΩ
50 V continuous, 100 V at max. duration of 1 ms
(sampling ratio 1:20)
Supported
Yes, can be assigned parameters in 4 steps by
means of digital filtering
Step
None
Weak
Medium
Strong
2AI U HS analog electronic module (6ES7134-4FB51-0AB0)
Time constant
1 x cycle time
64 x cycle time
128 x cycle time
512 x cycle time
Manual, 04/2007, A5E01076015-01