DSC TL2803GR Installation Manual page 39

Hide thumbs Also See for TL2803GR:
Table of Contents

Advertisement

[983] Firmware Update Diagnostics Section
Firmware updates for panel and the communicator itself can be made from the communicator.
Table 16: Response Code Descriptions and Corresponding Actions
Response
Description of Response Code
Code
Bad File
00
Version check failed
01
Image type mismatch
02
Device type mismatch
03
Hardware type mismatch
04
General variant mismatch
05
Firmware header wrong length
Panel is Busy
20
System update pending - panel is armed
System Update Pending -AC Trouble
21
(Any AC Trouble; Device/Module)
System Update Pending -Low Battery
22
(Any Low Battery Trouble; Device/Module)
System update pending - communication in
25
progress
Firmware Update Sequence Change
A0
System firmware update successful
A1
System firmware update failure
System firmware update failure - module not
A2
found
AA
Device firmware transfer begin
AB
Device firmware module update begin
AC
General device firmware transfer failure
Firmware Update Status
C0
System ready to update
C1
System update cancel request received
C2
System update begin
Firmware Download Request Reject
E0
E1
E2
E3
E4
E5
Remote firmware update disabled
Local Status Update States
FE
Firmware file empty
FD
Firmware download in progress
The table above displays the firmware update indicator codes and meaning of each code. The
updates can be made from the communicator. Communicator can update panel firmware and also
of the communicator itself. This section does not provide specific details such as if the image is
still stored or erased due to the cancellation code.
HSPA(3G) Alarm Communicator Installation Manual
Corresponding Action
Contact DSC Tech Support, describe the action attempted
with the system and supply them with the Response Code in
Section [983].
Disarm the panel to continue with system firmware update
process.
Resolve the AC trouble to continue with system firmware
update process.
Resolve the Low Battery Trouble to continue with system
firmware update process.
Retry in a few minutes; if issue persists, contact DSC Tech
Support.
None
At least one module was not updated. Use DLS to reapply the
firmware to the module not updated.
At least one module was not responding during firmware
update. Ensure all modules enrolled are physically connected
and powered up.
None
None
Contact DSC Tech Support, describe the action attempted
with the system and supply them with the Response Code in
Section [983].
None
The system has received an update cancel request from DLS.
None
Reserved
Enable remote firmware update in the communicator in order
to perform remote system firmware update.
No action required. Communicator currently does not have
any firmware files.
No action required. Communicator is currently downloading
firmware.
39

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents