Optional Built-On And Built-In Accessories - Siemens SIMOTICS SD Operating Instructions Manual

Low-voltage motors
Table of Contents

Advertisement

Installation altitude: ≤ 1000 m
Air with normal oxygen content, usually 21 % (V/V)
If the environmental requirements are different from the details listed here, then the values
on the rating plate will apply.
Machines intended for use in Zone 1 (type of protection Flameproof Enclosure "d" or
Increased Safety "e") or in Zone 2 (type of protection "n") are designed with IP 55 degree of
protection.
Machines intended for use in Zone 21 have IP 65 degree of protection. Machines intended
for use in Zone 22 have IP 55 degree of protection and can be used in dusty environments
such as grinders, silos, animal feed plants, and malthouses, as well as in certain areas of the
chemical industry.
3.3.8

Optional built-on and built-in accessories

In addition to the current-dependent overload protective device located in the connecting
leads, we recommend that you use temperature sensors embedded in the stator winding in
order to monitor the temperature and protect the stator winding from overheating.
Machines whose winding is exposed to the danger of condensation due to the climate, e.g.
machines at a standstill in a damp environment or machines which are exposed to large
temperature fluctuations, can be equipped with an anti-condensation heater.
As an option, the machines can be fitted with additional built-on accessories on the
ventilation side (e.g. brake, rotary pulse encoder).
Optional built-on and built-in accessories for explosion-proof machines
Investigate the influence of sources of heat and cold on the finished installation when it
includes built-on accessories compliant with EN 60079-14!
Table 3- 5
Recommended maximum interface temperatures for flange motors
Type of protection
Supply voltage
Control range
Cooling method
Frame size
Mechanical design
Ambient temperature
Temperature class
Number of poles
Max. shaft temperature
Max. flange temperature
Select mounted equipment such as brakes, forced ventilation or incremental encoders according to the
requirements of the Directive 94/9/EC.
Low-voltage motors
Operating Instructions, 05/2014, 5 610 00000 02 000
Ex d
Line
Converter
-
10 Hz to f
rated
-20° C ... +60° C
T3, T4
2, 4
100 °C
100 °C
(≤ 60 Hz)
Self-ventilated
63 ... 200
EN 50347
-20 °C ... +40 °C
2
60 °C
60 °C
Description
3.3 Installation
Ex e, Ex nA
Line
-
T3
4
75 °C
75 °C
25

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotics gpSimotics dpSimotics xp

Table of Contents