Omron GI-SID1224 Safety Precautions page 2

Safety i/o terminal

Advertisement

Safety I/O Terminal
GI-SMD1624
GI-SID1224
EN
Safety Precautions
Thank you for purchasing a Safety I/O Terminal.
To ensure the safe usage of the product, read and understand this
document, the manuals for Safety I/O Terminal, CPU Unit, Communication
Control Unit, and the manuals for all other Units.
Contact your OMRON representative and make sure that you use the most
recent version of each manual.
Keep this document, and all relative manuals in a safe place, and make sure
that they are delivered to the final user of the product.
OMRON Corporation
2018
© OMRON Corporation
All Rights Reserved.
5382608-8A
Trademarks
®
• EtherCAT
is registered trademark and patented technology, licensed
by Beckhoff Automation GmbH, Germany.
• ODVA, CIP, CompoNet, DeviceNet, and EtherNet/IP are trademarks of
ODVA.
Other company names and product names in this document are the
trademarks or registered trademarks of their respective companies.
EU Declaration of Conformity
OMRON declares that GI-S Series Safety I/O Terminals conform
with the requirements of the following EU Directives:
EMC Directives: 2014/30/EU
Machinery Directive: 2006/42/EC
Standards
GI-S Series Safety I/O Terminals are designed and manufactured in
accordance with the following standards:
• EN ISO 13849-1: 2015 PLe/Safety category 4
• IEC/EN 62061 SIL CL3
• EN 61131-2
Safety Precautions
●Definition of Precautionary Information
Indicates a potentially hazardous situation which, if
not avoided, will result in minor or moderate injury, or
WARNING
may result in serious injury or death. Additionally
there may be significant property damage.
Indicates a potentially hazardous situation which, if
not avoided, may result in minor or moderate injury,
CAUTION
or property damage.
●Alert Statements
WARNING
Required safety functions will be lost, and death due to injury
may possibly occur.
Do not use GI-S Series' test output as the safety output line.
Required safety functions will be lost, and death due to injury
may possibly occur.
Do not use non-safety signals, including explicit messages and
exposed variables, as safety signals.
Death due to injury may possibly occur.
LEDs are NOT reliable indicators and cannot be guaranteed to
provide accurate information. They should ONLY be used for
general diagnostics during commissioning or troubleshooting. Do
not attempt to use LEDs as operational indicators.
Death due to injury may possibly occur.
Never ground the +24-V side of the power supply. Safety
functions may not operate correctly due to ground faults.
When building the system, observe the following warnings listed
on the reference manual to ensure the integrity of the
safety-related components: "Setting Up a Risk Assessment
System", "Protective Measure", "Role of Safety Products",
"Installing Safety Products", "Observing Laws and Regulations",
"Observing Usage Precautions", and "Transferring Devices and
Equipment".
Death due to injury may possibly occur.
Clear the memory to delete the previous configuration data
stored in the Safety I/O Terminal unit before installing the Safety
I/O Terminal to the equipment or device, or connecting to a
network.
Death due to injury may possibly occur.
Before connecting a Safety I/O Terminal to the network, set a
suitable IP address and communications speed.
Required safety functions will be lost, and death due to injury
may possibly occur.
Verify the calculated reaction times for all safety chains to confirm
that they satisfy the required specifications.
Required safety functions will be lost, and death due to injury
may possibly occur.
Make sure that the originator and target have the proper
configuration if you want to set the Open type as "Open only".
Required safety functions will be lost, and death due to injury
may possibly occur.
In debugging safety I/O terminals, check that the safety I/O
terminals and the external devices operate properly as
programmed by the CPU Unit which is an originator device.
Death due to injury may possibly occur.
Before you start the system, perform user testing to make sure
that the configuration data of all devices are correct and they
operate correctly.
Required safety functions will be lost, and death due to injury
may possibly occur.
Do not disassemble, repair, or modify the product.
Death due to injury may possibly occur.
Take appropriate and sufficient countermeasures when installing
the product in the following locations.
a) Locations subject to strong, high-frequency noise
b) Locations subject to static electricity or other forms of noise
c) Locations subject to strong electromagnetic fields
d) Locations subject to possible exposure to radioactivity
e) Locations close to power lines
CAUTION
Fire or malfunction may possibly occur if screws loosen.
Tighten terminal block fixing screws to the torques specified in
the reference manual.
Moderate burn injury may possibly occur. Do not touch any device
when power is being supplied or immediately after the power
supply is turned OFF.
Precautions for Safe Use
■Transporting/Installation/Wiring
• Do not drop any product or subject it to abnormal vibration or shock. Doing so may
result in injury, product malfunction or burning.
• Do not operate or store the product in the following locations. Doing so may result in
burning, in operation stopping, or in malfunction.
a) Locations subject to direct sunlight
b) Locations subject to temperatures or humidity outside the range specified in the
specifications
c) Locations subject to condensation as the result of severe changes in
temperature
d) Locations subject to corrosive or flammable gases
e) Locations subject to dust (especially iron dust) or salts
f) Locations subject to exposure to water, oil, or chemicals
g) Locations subject to shock or vibration
h) Locations subject to noise due to static electricity
• This is a Class A product (for industrial environments). In a residential environment,
it may cause radio interference. If radio interference occurs, the user may be
required to take appropriate measures.
• Use the GI-S Series in the enclosure complying with IP54 (IEC/EN 60529) or higher.
• In installing to the control panel, use DIN Tracks (TH35-7.5/TH35-15: IEC60715). In
order to prevent drops due to vibration, fix the GI-S Series to the DIN Tracks using
End Plates (sold separately).
• Install the product in a well-ventilated area. Avoid installing the product near heating
elements. Doing so may result in malfunction, in operation stopping, or in burning.
• Follow the instructions in the reference manual to correctly perform installation and
wiring.
• Use the methods that are specified in the reference manual for wiring the terminal
blocks.
• When you install wiring, be sure to turn off the power beforehand. Otherwise, the
external devices connected with the GI-S Series may operate unexpectedly.
• Use the correct wire size, wiring parts and tools when you wire the system.
Otherwise, cables may be disconnected to cause short-circuit or wire breakage.
• Make sure that the current capacity of the wire is sufficient. Otherwise, excessive
heat may be generated. When cross-wiring terminals, the total current for all the
terminals will flow in the wire. When wiring cross-overs, make sure that the current
capacity of each of the wires is not exceeded.
• Make sure that foreign material or metal dust should not come into the Safety I/O
Terminal while wiring and/or installation. Doing so may result in product burning,
electric shock, or failure.
• When you insert a flat-blade screwdriver into a release hole on the screwless
clamping terminal block, press the screwdriver down with an appropriate angle and a
force of 30 N or less. Applying excessive force may damage the terminal block.
• Do not tilt or twist the flat-blade screwdriver while it is pressed into the release hole
of the screwless clamping terminal block. Doing so may break the terminal block.
• Do not pull on the cables or bend the cables beyond their natural limit. Do not place
any heavy objects on the cables or other wiring lines. Doing so may severe the
cables.
• Mount terminal blocks and connectors only after checking the mounting location
carefully. During this time, be careful not to pinch your fingers.
• Be sure that the terminal blocks and Ethernet communications cables with tightening
screws or locking devices are properly tightened to or locked into place.
• DC power supplies must meet the following items:
a) Use reinforced insulation or double insulation.
b) Ensure an output hold time of 20 ms min.
c) Use an SELV power supply that meets the requirements of IEC/EN 60950-1 and
EN 50178.
• Select a unit power and output power supply with sufficient capacity by considering
the power supply capacity or inrush current when the power is turned ON that is
specified in the reference manual. Otherwise, the external power supply may not be
turned ON or malfunction due to unstable power supply voltage.
• Use the unit power supply and output power supply within the operating power
supply voltage range specified on the reference manual.
• Do not apply voltages that exceed the rated value or connect loads to the GI-S
Series Terminals.
• Surge current occurs when the power supply is turned ON. When selecting fuses or
breakers for external circuits, consider the fusing and sensing characteristics to
select fuses or breakers with appropriate specification. Refer to the reference manual
for surge current specifications.
■Operation/Maintenance
• Always turn OFF the power supply to the Safety I/O Terminal before you attempt any
of the following.
1) Assembling the Units
2) Setting rotary switches
3) Connecting cables or wiring the system
4) Connecting or disconnecting the terminal blocks or connectors
5) Attaching or removing the memory cassette
The V0 indicator for the controller remains lit for several seconds after power is
turned off. Make sure that the V0 indicator is not lit before you perform any of the
above operations.
• Avoid applying excessive force when you change the rotary switch settings.
• Insert the memory cassette all the way. And also, do not remove the memory
cassette while the power is being supplied. Data may become corrupted, and the
product will not operate correctly if it uses corrupted data.
• Always confirm safety before you transfer data or setting values from the Sysmac
Studio. During transfer, do not disconnect the cable or turn OFF the power supply to
the Safety I/O Terminal.
• If EtherNet/IP tag data links (cyclic communications) are used with a repeating hub,
the communications load on the network will increase. This will increase collisions
and may prevent stable communications. Do not use repeating hubs on networks
where tag data links are used. Use an Ethernet switch instead.
• Make sure to use the communications distance and method of connection for
EtherNet/IP within specifications. Do not connect EtherNet/IP communications to
Ether-CAT or other networks. An overload may cause the network to fail or
malfunction.
■Disposal
Dispose of the product in accordance with the relevant rules and regulations of the
country or area where the product is used.
Reference Manuals
Model numbers / Manual name
GI-S□□□□□□
GI-S series
Z400
Safety I/O Terminal
User's Manual
NX-series
Z395
NX-SL5□□□
Safety Control Unit / Communication
NX-SI□□□□
NX-SO□□□□
Control Unit
NX-CSG□□□
User's Manual
SYSMAC-SE2□□□
Sysmac Studio Version 1
W504
Operation Manual
Suitability for Use
Omron Companies shall not be responsible for conformity with any standards, codes or regulations
which apply to the combination of the Product in the Buyer' s application or use of the Product. At
Buyer' s request, Omron will provide applicable third party certification documents identifying ratings
and limitations of use which apply to the Product. This information by itself is not sufficient for a
complete determination of the suitability of the Product in combination with the end product,
machine, system, or other application or use. Buyer shall be solely responsible for determining
appropriateness of the particular Product with respect to Buyer' s application, product or system.
Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A
WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT
(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL
EQUIPMENT OR SYSTEM.
OMRON Corporation (Manufacturer)
Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 JAPAN
Contact: www.ia.omron.com
Cat. No.
Regional Headquarters
OMRON ELECTRONICS LLC
OMRON EUROPE B.V.
Wegalaan 67-69,2132 JD Hoofddorp
2895 Greenspoint Parkway, Suite 200
The Netherlands
Hoffman Estates, IL 60169 U.S.A.
Tel: (31)2356-81-300
Tel: (1) 847-843-7900
Fax: (31)2356-81-388
Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
No. 438A Alexandra Road #05-05/08
(Lobby 2), Alexandra Technopark,
200 Yin Cheng Zhong Road,
Singapore 119967
Pu Dong New Area, Shanghai,
Tel: (65) 6835-3011
200120, China
Fax: (65) 6835-2711
Tel: (86) 21-5037-2222
Fax: (86) 21-5037-2200
Note: Specifications subject to change without notice.