Corner Rear Venting Graph
Measure the vertical height from the fireplace hearth to the centre of
the termination and the horizontal run from the fireplace flue collar to
the wall flange of the termination. Plot on the Venting Graph with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Selection of components and details of venting layout should adhere
to the following guidelines:
• Vent terminations must not be recessed in walls or siding.
• For Heat Shield requirements see Section 3-3.
• Once the proposed venting layout has been determined refer to
graph to ensure the layout is acceptable.
Notes Wall Mounted Terminations: REAR VENT
• All measurements for vertical or horizontal runs are measured from
center of the vent pipe.
• Venting runs must fall within the limits set by the venting graph.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 114" and the horizontal
run to the wall flange of the vent termination is 126", this would be an
acceptable installation.
Example B: (Unacceptable Installation)
If the vertical dimension from the hearth is 66" and the horizontal run
to the wall flange of the vent termination is 84", this would not be an
acceptable installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the floor of the fireplace is 72" and the
horizontal run to the wall flange of the vent termination is 144", this
would not be an acceptable installation.
REAR VENT RUN
132
120
Acceptable vent run
within non-shaded area.
108
96
A
84
72
60
48
64''
36
24
12
0
0
12
24
36
48
60
Horizontal Run (In.)
Figure 9. Rear Vent Venting Graph for wall mounted terminations
20
B
C
59''
Unacceptable vent run
within shaded area.
72
84
96
108
120
132
144
156
168 180
Flex or Rigid
Hearth
Figure 8. Rear Vented, wall mounted Multi-elbow termination installation. must have a mini-
mum vertical rise of 26"
Installation
64''
Max.
26''
Min.
59''
Min.
18''
Max.
33''
XG0229 - 112718