Weil McLain 88 Series 2
Boiler
Burner
Firing Mode
488
CG10
Low Fire Start
588
CG25
688
CG25
788
CG50
888
CG50
988
CG50
1088
CG50
1188
CG50
1288
CG50
1388
CG50
Commercial Gas Burner OEM Setup Guide
Rate
MBH
986
Mod
676 / 1357
Mod
784 / 1729
Mod
904 / 2017
Mod
1030 / 2396
Mod
1055 / 2666
Mod
1228 / 3089
Mod
1458 / 3403
Mod
1462 / 3762
Mod
1719 / 4171
Manifold
Head Type
Pressure
/ Head
in. water
Setting
1.5 / 4.5
10.6S / 10.6
0.8 / 3.5
25.1S / 25.1
0.8 / 3.7
25.2S / 25.2
0.6 / 3.1
50.1S / 50.1
0.5 / 3.05
50.2S / 50.2
0.6 / 3.75
50.2S / 50.2
0.55 / 3.65
50.3S / 50.3
0.6 / 3.6
50.4S / 50.4
0.6 / 4.15
50.4S / 50.4
0.65 / 4.0
50.5S / 50.5
Damper
Shutter
Setting
Band
Blue / Red
Settings
-
10/4
16 / 41
-
22 / 53
-
19 / 32
-
20 / 39
-
20 / 43
-
21 / 48
-
23 / 53
-
23 / 75
-
26 / 70
-
Air Tube
Insertion
Inches
4.00"
4.00"
4.00"
4.00"
4.00"
4.00"
4.00"
4.00"
4.00"
4.00"