Pump Out For Heat Recovery Systems - LG Multi V5 Service Manual

Hide thumbs Also See for Multi V5:
Table of Contents

Advertisement

OTHER CONTROLS
Setting Optional Modes

Pump Out for Heat Recovery Systems

Example of Pump Out Function When Slave2 Outdoor Unit Experiences Inverter Compressor Failure.
Closed
Open
Slave 2 Outdoor Unit
Heating Mode
Liquid
Low
Pipe
Pressure
Vapor Pipe
1. Verify the liquid pipe and low pressure vapor pipe of the outdoor
unit are closed for Pump Out operation. Open the high pressure
vapor pipe service valve.
2. Operate Pump Out function.
3. Close high pressure vapor pipe of unit after Pump Out is
complete.
4. Replace inverter compressor, eliminate remaining refrigerant of
the corresponding outdoor unit, and perform Vacuum procedure
using Vacuum Mode.
5. Add refrigerant using the Refrigerant Auto Charge Function.
78
Slave 1 Outdoor Unit
Heating Mode
High
Liquid
Pressure
Pipe
Vapor Pipe
Refrigerant Charging Valve
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Low
High
Pressure
Pressure
Vapor Pipe
Vapor Pipe
Figure 28: Close Up of Heat Recovery Service Ports and Refrigerant
Charge Valve.
Liquid Pipe
Vapor Pipe
Master Outdoor Unit
Heating Mode
Liquid
Low
High
Pipe
Pressure
Pressure
Vapor Pipe
Vapor Pipe
Service Ports