Sw05M Function (Rotary Switch For Addressing Heat Recovery Units); Due To Our Policy Of Continuous Product Innovation, Some Specifications May Change Without Notification - LG Multi V5 Service Manual

Hide thumbs Also See for Multi V5:
Table of Contents

Advertisement

If large capacity indoor units (larger than 54,000 Btu/h) are installed, the Y-branch pipe shown in the table below must be used to twin the ports.
Kit Model
Vapor Pipe Dimensions
No.
I.D. 7/8
I.D. 1
I.D. 3/4
1
ARBLN03321
15-3/8
16-1/4
I.D. 1-1/8
I.D. 7/8
O.D. 3/4
3
3-3/16
2-3/4

2. SW05M Function (Rotary Switch for Addressing Heat Recovery Units).

• Rotary switch SW05M must be set to "0"' when install-
ing only one heat recovery unit.
• When installing multiple heat recovery units, address
each unit with sequentially increasing numbers start-
ing from "0".
Addressing
Non-zoning (Normal Setting).
• Set the address of the heat recovery unit valve to the central control address of the connected indoor unit.
• SW01M: Select the valve to address.
• SW03M: Increases the valve address by ten (10).
• SW04M: Increases the valve address by one (1).
Each indoor unit must have a unique, preset central control address (using its wired controller) before manual valve addressing can occur.
Table 56: Settings for Manual Valve Addressing, Non-Zoning.
PCB Component
SW01M
ON
OFF
2 3 4
1
1 2
3
4
HEAT RECOVERY UNIT SETTINGS
Vapor Pipe
Model No.
I.D. 3/4
I.D. 5/8
I.D. 1/2
2
I.D. 3/4
3-5/16
I.D. 5/8
I.D. 1/2
AJR54072906
3
I.D. 7/8
O.D. 1
O.D. 3/4
I.D. 1
1
2
4-3/8
Figure 45: Adjusting the Heat Recovery Unit Addresses.
S/W No.
No. 1
No. 2
No. 3
No. 4
SW03M
SW04M

Due to our policy of continuous product innovation, some specifications may change without notification.

©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Liquid Pipe Dimensions
I.D. 1/2
I.D. 3/8
I.D. 1/4
I.D. 3/8
I.D. 1/2
I.D. 1/2
I.D. 3/8
I.D. 1/4
12-5/8
13-1/16
A B
A B
3 4
1 2
Set Up
Manual Addressing Valve No. 1
Manual Addressing Valve No. 2
Manual Addressing Valve No. 3
Manual Addressing Valve No. 4
Increases the Valve Address by Ten (10)
Increases the Valve Address by One (1)
Unit: Inch
Liquid Pipe
Model No.
AJR54072902
2-15/16
A B
3 4
1 2
1 2
3 4
101