Specifications Of Electrical Parts; Rav-Gm561At P , Gm801Atp - Toshiba RAV-GM561ATP-E Service Manual

Outdoor unit, digital inverter
Hide thumbs Also See for RAV-GM561ATP-E:
Table of Contents

Advertisement

5. SPECIFICATIONS OF ELECTRICAL PARTS

, GM801AT
*
*
RAV-GM561AT
P
No.
Parts name
1
Compressor
2
Fan motor
3
4-way valve coil
4
PMV coil
5
High-pressure SW
6
Reactor
7
P.C. board
8
Fuse (Mounted on P.C. board)
9
Fuse
10
Fuse (Mounted on P.C. board)
11
Outdoor temp. sensor (TO sensor)
12
Heat exchanger temp. sensor (TE sensor)
13
Suction temp. sensor (TS sensor)
14
Discharge temp. sensor (TD sensor)
15
Heat exchanger temp. sensor (TL sensor)
16
Compressor thermo. (Protection)
RAV-GM1101AT
*
P
*
,GM1401AT
No.
Parts name
1
Compressor
2
Fan motor
3
4-way valve coil
4
PMV coil
5
High-pressure SW
6
Reactor
7
P.C. board
8
Fuse (Mounted on P.C. board)
9
Fuse
10
Fuse (Mounted on P.C. board)
11
Outdoor temp. sensor (TO sensor)
12
Heat exchanger temp. sensor (TE sensor)
13
Suction temp. sensor (TS sensor)
14
Discharge temp. sensor (TD sensor)
15
Heat exchanger temp. sensor (TL sensor)
16
Compressor thermo. (Protection)
*
*
P
DX150A1T-20F
ICF-140-43-4R
STF-H01AZ1724A1
PQ-M01012-000082
ACB-4UB83W
CH-57-Z-T
MCC-1645
CS-12AL
*
P
*
DX330A2T-20M
WDF-340-A100-1
STF-H01AZ1724A1
CAM-MD12TF-18
ACB-4UB83W
CH-62
MCC-1648
CS-12AL
- 30 -
Type
3 phase, 4P, 1100 W
Output 43 W
OFF:4.15MPa
8.88~10mH, 16A
-
AC250 V, 25 A
-
AC250 V, 6.3 A
-
AC250 V, 3.15 A
-
10 kΩ at 25°C
-
10 kΩ at 25°C
-
10 kΩ at 25°C
-
50 kΩ at 25°C
-
50 kΩ at 25°C
OFF: 125 ± 4°C, ON: 90 ± 5°C
Type
3 phase, 4P, 3000W
Output 100 W
OFF:4.15MPa
5.34~5.99mH, 18.5A
-
AC250 V, 25 A
-
AC250 V, 10 A
-
AC250 V, 3.15 A
-
10 kΩ at 25°C
-
10 kΩ at 25°C
-
10 kΩ at 25°C
-
50 kΩ at 25°C
-
50 kΩ at 25°C
OFF: 125 ± 4°C, ON: 90 ± 5°C
FILE NO. SVM-18043
Specifications
-
-
-
Specifications
-
-
-