Outdoor Unit - Toshiba RAV-GM561ATP-E Service Manual

Outdoor unit, digital inverter
Hide thumbs Also See for RAV-GM561ATP-E:
Table of Contents

Advertisement

3-2. Outdoor Unit

RAV-GM561AT P
TS sensor
P
TD sensor
4-way valve
(STF-H0108)
Ø19.05 × 160L
Rotary compressor
(DX150A1T-20F)
(MPa)
Pd
Standard
3.11
Cooling
Overload
3.37
Low load
1.90
Standard
2.27
Heating
Overload
2.86
Low load
1.86
* 4 poles are provided to this compressor.
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
Pressure
switch
2-step muffler
Ø19 .05 × 200L
Muffler
Pressure
Pipe surface temperature (°C)
(kg/cm
G)
2
Discharge
(TD)
Ps
Pd
Ps
0.96
31.7
9.8
90
1.08
34.4
11.0
77
0.70
19.4
7.1
48
0.63
23.1
6.4
82
0.89
29.2
9.1
86
0.25
19.0
2.6
69
Packed valve
Outer dia. Ø12.7
TŌ sensor
TL sensor
TE
sensor
Heat exchanger
Ø7 ripple, 2 rows,
24 steps
FP1.3 flat fin
Indoor heat
Outdoor heat
Suction
exchanger
exchanger
(TS)
(TC)
(TE)
13
12
43
21
17
53
7
5
30
2
36
1
17
47
11
-14
31
-15
- 25 -
FILE NO. SVM-18043
Packed valve
Outer dia. Ø6.35
PMV
(Pulse Motor Valve)
(DPF(S01)1.8C-15)
Strainer
Distributor
R32 : 0.9 kg
Cooling
Heating
Indoor/Outdoor
Compressor
temp. conditions
revolutions per
Indoor
(DB/WB) (°C)
second (rps)
fan
*
Indoor
60
HIGH
27/19
35
HIGH
32/24
50
LOW
18/15.5
65
HIGH
20/-
95
LOW
28/-
98
HIGH
15/-
Outdoor
35/-
46/-
-5/-
7/6
24/18
-10/(70%)