9-2. Air Conditioner Does Not Operate

9-2-1. Circuit breaker trips (or fuse blows)
A. When the circuit breaker is set to ON, it is tripped soon. (Resetting is not possible.)
There is a possibility of ground fault.
Check insulation resistance.
If resistance value is 1MΩ or less, insulation is defective ("NO").
WARNING
*
Set circuit breaker to OFF.
1 Remove both power supply wires
and inter-unit wires from terminal
plate in outdoor unit.
Measure insulation resistance
of outdoor unit.
2 Remove inter-unit wires from
terminal plate in indoor unit.
Measure insulation resistance
of indoor unit.
B. Circuit breaker trips in several minutes after turning the air conditioner on.
There is a possibility of short circuit.
Check capacity of circuit breaker.
Capacity of circuit breaker is
suitable.
Measure resistance of outdoor fan
motor winding.
Measure resistance of compressor
motor winding.
(Inter-unit)
INDOOR
Power lines
INDOOR UNIT
Terminal
2
1
2
3
Disconnect
switch
(Field supply)
G
Grounding
line
NO
NO
NO
45
OUTDOOR UNIT
Terminal
1
1
Fuse
2
3
1
4
L1
5
Circuit
L2
breaker
6
G
Ground
Insulation of
outdoor unit
is defective.
Measure insulation
resistance of electrical
parts in outdoor unit.
Insulation of
indoor unit
is defective.
Measure insulation
resistance of electrical
parts in indoor unit.
Replace with suitable
one (larger capacity).