Important Please Read Before Starting When Installing …………………………………………………………………… …In a Room This air conditioning system meets strict safety and operating Properly insulate any tubing run inside a room to prevent standards. As the installer or service person, it is an important “sweating”...
Table of Contents OPERATING RANGE ..................5 SPECIFICATIONS .................... 6 (1) Unit Specifications ..................6 (2) Major Component Specifications ..............8 (A) Indoor Unit .................... 8 (B) Outdoor Unit ..................9 (3) Other Component Specifications .............. 10 (A) Indoor Unit ..................10 (B) Outdoor Unit ..................
Page 4
Introduction: Read Me First! This manual will help you understand and service the air conditioner. To help you find the information you need, we have divided it into 5 main sections. Each section is divided into chapters with charts, tables and explana- tions to help you find and repair problems.
1. OPERATING RANGE XS1852 / C1852 Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum 95 F DB / 71 F WB 115 F DB Minimum 67 F DB / 57 F WB 67 F DB XS1852 / CL1852 Temperature Indoor Air Intake Temp.
6. REFRIGERANT FLOW DIAGRAM Indoor Unit: XS1852 Outdoor Unit: C1852, CL1852 Indoor Unit Outdoor Unit Wide tube Wide tube service valve Accumulator O. D. 5/8" (15.88 mm) Narrow tube Capillary Narrow tube service valve tube O. D. 1/4" (6.35 mm)
UNIT will be within the limits given in Table 1. 0711_M_I Fig. 1 Table 1 Models C1852 Tubing Data CL1852 Narrow tube in. (mm) 1/4 (6.35) : Thickness 0.0314" (0.8 mm) Tubing size outer dia.
Page 18
7. INSTALLATION INSTRUCTIONS Selecting the Installation Site Indoor Unit AVOID: areas where leakage of flammable gas may be expected. places where large amount of oil mist exist. direct sunlight. locations near heat sources which may affect performance of the unit. locations where external air may enter the room directly.
Page 19
7. INSTALLATION INSTRUCTIONS Exhaust fan Outdoor Unit Hot air AVOID: Heat source heat sources, exhaust fans, etc. (Fig. 3) Out- door damp, humid or uneven locations. unit 1817_C_I choose a place as cool as possible. Fig. 3 choose a place that is well ventilated. Obstacle above allow enough room around the unit for air intake/ exhaust and possible maintenance.
Page 20
7. INSTALLATION INSTRUCTIONS Electrical Wiring (7) Regulations on wire diameters differ from General Precautions on Wiring locality to locality. For field wiring rules, (1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, please refer to your LOCAL ELECTRI- then carry out the wiring closely following CAL CODES (ex.
Page 21
Circuit Max. Wire Capacity Capacity AWG #12 AWG #12 Diameter C1852, CL1852 75 ft. 65 ft. 15 A 20 A AWG #12 *1 Refer to the Wiring System Diagrams (See below diagram) for the meaning of “A”, “B”. AWG = American Wire Gauge...
8. ELECTRICAL DATA Electrical characteristics Indoor model: XS1852 / Outdoor model: C1852, CL1852 Indoor Unit Outdoor Unit Complete Unit Fan Motor Fan Motor Compressor Performance at 230 - 208 V / 1 phase / 60 Hz 230 - 208 V / 1 phase / 60 Hz 0.60 - 0.60...
10. PROCESSES AND FUNCTIONS Room Temperature Control The Unit adjusts room temperature by turning the outdoor unit’s compressor ON and OFF. This process is controlled by the thermostat located in the remote control unit. The figures on this and the next pages show how each part of the system performs when the room temperature changes and the thermostat activates the compressor to start (thermo ON) or stop (thermo OFF).
10. PROCESSES AND FUNCTIONS Freeze Prevention Freeze Prevention keeps the indoor heat exchange coil from freezing. Freezing reduces the efficiency of the unit, and frost buildup on the coil blocks cool air circulation from the indoor unit’s fan. FREEZE FREEZE PREVENTION PREVENTION MORE THAN 10 MINUTES...
10. PROCESSES AND FUNCTIONS Outdoor Fan Speed Control (CL1852) Low ambient fan speed control • This function protects the compressor from being damaged due to flowback of the liquid refrigerant to the compressor when the outdoor temperature is very low. •...
11. SERVICE PROCEDURES (1) Troubleshooting Check before and after Troubleshooting Many problems may happen because of wiring or power supply problems, so you should check these areas first. Problems here can cause false results in some of the other tests, and so should be corrected first. 1 1 1 1 1 Check power supply wiring (a) Single-phase...
Page 31
11. SERVICE PROCEDURES Air Conditioner does not Operate 1 1 1 1 1 Circuit breaker trips (or fuse blows). (a) When the circuit breaker is set to ON, it is tripped soon. • There is a possibility of ground fault. •...
Page 32
11. SERVICE PROCEDURES (b) Circuit breaker trips in several minutes after turning the air conditioner on. • There is a possibility of short circuit. • Check capacity of circuit Replace it with a breaker. suitable one. Is capacity of circuit (= larger capacity) breaker sufficient ? •...
Page 33
11. SERVICE PROCEDURES C. Check “Operation selector” switch in the indoor unit. • Has “Operation selector” IND. LAMP Ass’y or P.C.B. switch been set to ON Ass’y in the indoor unit position ? is defective. Set “Operation selector” switch to ON. But neither unit runs.
Page 34
11. SERVICE PROCEDURES F. Check indoor fan motor thermal protector (49FMI) • Disconnect the socket from 9P (WHT) connector. • Check the continuity between No. 8 and No.9 poles of the 9P socket. No continuity. The thermal protector (49FMI) is operated. Check fan casing Remove foreign Fan cannot...
Page 35
11. SERVICE PROCEDURES Outdoor Unit does not Run. A. Check COOL / FAN selector switch in the remote control unit. • Is COOL/FAN selector switch Set to COOL. set to COOL ? 0623_X_S B. Check set temperature. Try to lower set temperature by Temperature setting button “COOLER”.
Page 36
11. SERVICE PROCEDURES C. Check compressor motor magnetic contactor. • Check coil resistance of compressor motor magnetic contactor. (PR) 1896_X_S Check outdoor unit P.C.B. D .Check indoor unit P.C.B. (CL1822 Type) • Check P.C.B. Ass’y. • Check P.C.B. Ass’y. • Check voltage between •...
Page 37
11. SERVICE PROCEDURES Indoor Unit does not Run. (Indoor fan and louver motor do not run.) P.C.B. Ass’y is defective. 0630_X_S Some Part does not Operate. A. Indoor fan does not run. Check fan casing Remove foreign for foreign matter matter or repair.
Page 38
11. SERVICE PROCEDURES Outdoor Fan does not Run. • Check fan casing Remove foreign for foreign matter matter or repair. Fan cannot on the inside. be rotated. • Check fan rotation. Rotate the fan gently once or twice by hand. •...
Page 39
11. SERVICE PROCEDURES Poor Cooling Check installation position Change installation of remote control unit. position of remote • Does cool air from air condi- control unit. tioner reach remote control unit directly ? Insulate wide tube and • Is wide tube between indoor unit then execute taping with and outdoor unit insulated ? narrow tube.
11. SERVICE PROCEDURES A Sensor is Defective 1 1 1 1 1 Indoor (heat exchanger) coil temp. Sensor is defective. (a) Open (=No continuity in sensor) Compressor and outdoor fan repeat ON for 10 minutes and OFF for 6 minutes when sensor opens.
11. SERVICE PROCEDURES Checking the Electrical Components Earthed wire Clip Measurement of Insulation Resistance • The electrical insulation is acceptable Probe when the resistance exceeds 1 M . Insulation Fig. 13 tester 0638_X_S 1 1 1 1 1 Power Supply Wires Terminal plate Clamp the earthed wire of the Power Supply wires with a lead clip of the...
Page 42
11. SERVICE PROCEDURES Checking the Protective Devices • Disconnect the connector, which consists of P (plug) and S (socket) when you want to check the protective device. • Then check continuity among plug’s (and/or socket’s) terminal as in Fig. 17. •...
Page 43
11. SERVICE PROCEDURES Checking the Electrical Parts 1 1 1 1 1 Power transformer (TR1) ....Indoor unit *Measure the coil resistance. • Primary 230-208 V ; Measure the resistance between two WHT lead wire terminals of socket connected to power transformer. •...
Page 44
11. SERVICE PROCEDURES 6 6 6 6 6 Continuity of fuse on P.C.B. Ass’y • Check for continuity using a multim- eter as shown in Fig. 19. Fuse NOTE Method Used to Replace Fuse on PCB Ass’y 1042_X_S 1. Remove the PCB Ass’y from the Fig.
Page 45
• The specifications, designs, and information in this brochure are subject to change without notice. SANYO FISHER Service Company CENTRAL REGION 1739 Sands Place, Suite G Marietta, GA 30067 Phone: (770) 951-8284 Fax: (770) 951-2077 Sep. / ’2000 Printed in U.S.A.