10 Specifications

10
Specifications
Item
Model
Supported Messages
Option Conformance
Connector Type
Physical Layer Type
IP Address Setting
Communication Speed
Number of Connections
Duplex Mode
Address Startup Mode
Ambient Temperature
Humidity
Storage Temperature
Area of Use
Altitude
38
Table 41 Option Specifications
SI-EM3/V
• Read Multiple Registers (03H)
• Write Single Register (06H)
• Write Multiple Registers (10H)
• Read and Write Registers (17H)
Commands that support multiple registers have a maximum Read and Write size of 16 registers.
Modbus-IDA Passed
RJ45 8-pin Shielded Twisted Pair Cat 5e cable
Isolated Physical Layer
Programmable from drive keypad or network
Programmable from drive keypad or network:
10/100 Mbps, auto-negotiate.
Modbus TCP/IP: 10
Web Page Access: 2
Half-forced, Auto-negotiate, Full-forced
Static, BOOTP, DHCP
-10 °C to +50 °C (14 °F to 122 °F)
95% RH or lower with no condensation
-20 °C to +60 °C (-4 °F to 140 °F) allowed for short-term transport of the product
Indoor (free of corrosive gas, airborne particles, etc.)
1000 m (3280 ft.) or lower