Sensor resistances
Temperature/resistance
0°C
16325
5°C
12697
10°C
9952
Max. spread
Max. flow rate
Connection types
Device
Type
1)
CGB-
B23, B33, C13x
,
3)
75/100
C33x, C43x, C53,
C53x, C63, C83x,
C93x
Category: Germany II
Austria II
2ELL3P,
Mark "x" indicates that all components of the flue are sur-
1)
rounded by combustion air and meet higher requirements
for gas tightness.
For type B23, B33 the combustion air is drawn from the
2)
installation room (open flue gas combustion equipment).
In Switzerland, observe the G1 gas guidelines!
3)
For type C, combustion air is drawn through a sealed system
from the outside (room sealed combustion equipment).
42
25. Maintenance and design data
15°C
7857
20°C
6247
25°C
5000
A heat exchanger protective function is integrated into the CGB-75/100. This prevents
stresses in the material by limiting the maximum temperature differential between flow
and return. The output is restricted at 28 K and above. If 38 K is nevertheless reached, the
burner shuts down briefly without a fault message. This characteristic must be taken into
account when selecting the components (e.g. pumps, heat exchangers and cylinders).
Excessive flow velocities may lead to erosion.
Maximum flow rate at Q
Operating mode
Open flue Balanced
flue
moisture resistant
X
X
B33, C53, C83x
Switzerland I
2H3P,
2H
Temperature [°C]
30°C
40°C
50°C
:
max
Can be connected to
chimney
Balanced
flue
chimney
C43x
4028
60°C
2662
70°C
1800
80 °C
CGB-75/100
6000 l/h (100 l/min)
Air/flue gas
Certified
routing
balanced
flue
C13x
,
C63x
2)
C33x, C53x
3062555_201804
1244
876
628
Moisture
resistant flue
B23, C53x,
C83x, C93x