York Predator ZT037 Technical Manual page 41

R-410a, zt series, 3 - 5 ton, 60 hertz
Hide thumbs Also See for Predator ZT037:
Table of Contents

Advertisement

UNIT DESCRIPTION / MODEL
TEST CONFIGURATION
Indoor Blower Speed (RPM)
External Static Pressure (IWG)
Nominal Airflow (CFM)
Blower Motor BHP
Octave Center Freq. Hz
63
125
250
500
1000
2000
4000
8000
1. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Indoor Sound Power Levels (Horizontal Ducted Discharge, High Static Belt Drive)
UNIT DESCRIPTION / MODEL
TEST CONFIGURATION
Indoor Blower Speed (RPM)
External Static Pressure (IWG)
Nominal Airflow (CFM)
Blower Motor BHP
Octave Center Freq. Hz
63
125
250
500
1000
2000
4000
8000
1. Requires driven pulley #AK-56, normal high static pulley is an #AK-69.
2. Cooling Operation – ID blower, compressor and outdoor fan operating at 230 VAC.
• Tested in accordance with AHRI Standard 260-2001. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning
Equipment.
• Testing datum includes effect of standard inlet air filters.
• Test duct dimension: 18 in. wide x 28 in. high x 8 ft. long, no elbows.
• Test duct termination is flush with reverberant room wall.
• Duct end (sound reflection) corrections included: (7.2, 3.4, 1.2, 0.4, 0.1, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 2k, 4k, 8k) Hz respectively.
Johnson Controls Ducted Systems
1,012- 5.5 Turns Open Equivalent
1.0
2,000
1.04
ID Blower
Cooling
1
Only (dB)
Operation
76
78
70
73
68
70
61
62
61
62
57
58
56
56
50
50
896 - 3.5 Turns Open Equivalent
1.0
1,200
0.64
ID Blower
Cooling
2
Only (dB)
Operation
77
81
74
76
67
68
65
66
61
62
58
60
57
59
51
53
ZT061 / 5 Ton / High Static Belt Drive
Horizontal (Side Return) Ducted Inlet
1,134 - 3 Turns Open Equivalent
1.6
1,800
1.25
ID Blower
(dB)
Only (dB)
Operation
78
73
68
61
61
57
55
50
ZT037 / 3 Ton / High Static Belt Drive
Horizontal (Side Supply) Ducted Discharge
1,072 - Fully Closed Equivalent
1.6
1,100
0.93
ID Blower
(dB)
Only (dB)
Operation
83
76
70
67
67
63
62
56
5167821-YTG-J-0518
1,174 - 2 Turns Open Equivalent
Cooling
ID Blower
1
(dB)
Only (dB)
79
79
76
74
69
69
62
60
62
58
58
54
56
52
50
47
1,170 - 2.5 Turns Open Equivalent
Cooling
ID Blower
2
(dB)
Only (dB)
84
83
77
80
70
72
67
67
67
66
63
63
62
62
57
56
2.0
1,600
1.39
Cooling
1
Operation
(dB)
81
77
70
62
60
56
53
48
1
1
2.0
1,000
1.08
Cooling
2
Operation
(dB)
84
80
73
68
69
64
63
58
41