Pentair DigiTrace AMC-2B-2 Installation Instructions

Pentair DigiTrace AMC-2B-2 Installation Instructions

Double pole line-sensing thermostat for nonhazardous locations

Advertisement

Quick Links

Double pole line-sensing thermostat for nonhazarDous locations

installation instructions

4.5 in (114 mm)
4.0 in (102 mm)
8.0 in
(202 mm)
Removable
knob cover
6.0 in (152 mm)
Terminal
block
3⁄4 in NPT conduit entry
WARNING:
This component is an electrical device. It must be installed
correctly to ensure proper operation and to prevent shock or
fire. Read these important warnings and carefully follow all the
installation instructions.
THERMAL MANAGEMENT SOLUTIONS
AMC-2B-2
4.0 in
(102 mm)
4.5 in
(114 mm)
5.6 in
(142 mm)
Adjusting
Ø.28 in (7 mm)
mounting holes (2X)
knob
0.3 in (9 mm)
1.2 in
(30 mm)
0.8 in
(20 mm)
Component approvals and performance are based on the use of
specified parts only. Do not use substitute parts or vinyl electrical
tape to make connections.
EN-DigiTraceAMC2B2-IM-H56910      01/13
DEScRIpTION
The DigiTrace AMC-2B-2 thermostat is designed for controlling
heat-tracing systems in nonhazardous locations. The thermostat
functions as a DPST switch.
The DPST switch will enable and disable current flow in both
buses of the heat- tracing cable.
The AMC-2B-2 can be used to control heat- tracing circuits in a
pipe-sensing mode directly (see Figure 1 on back).
Note: Do not use this thermostat to control two separate heat-
tracing circuits.
ADDITIONAL MATERIAL REqUIRED
• AT-180 aluminum tape
AppROvALS

SpEcIfIcATIONS

Enclosure
NEMA 4X, polyurethane-coated cast-
aluminum housing, stainless-steel hardware
Entries
One 3/4 in. NPT conduit hub
Set point range
25°F to 325°F (–4°C to 163°C)
Sensor exposure
–40°F to 420°F (–40°C to 215°C)
limits
Housing exposure
–40°F to 160°F (–40°C to 71°C)
limits
Switch
DPST
Electrical rating
22 A at 208/240 Vac
Relay coil
208–240 Vac, 4 VA
Accuracy
±6°F (±3.3°C)
Deadband
2°F to 12°F (1.1°C to 6.7°C) above actuation
temperature
Set point
±3°F (±1.7°C)
repeatability
Sensor type
Fluid-filled (silicone) bulb and 9 ft (2.7 m)
capillary
Sensor material
300 series stainless steel
Connection
Screw terminals, 10–14 AWG (2–5 mm
terminals
2
)
1 / 2

Advertisement

loading

Summary of Contents for Pentair DigiTrace AMC-2B-2

  • Page 1: Installation Instructions

    Double pole line-sensing thermostat for nonhazarDous locations installation instructions DEScRIpTION The DigiTrace AMC-2B-2 thermostat is designed for controlling heat-tracing systems in nonhazardous locations. The thermostat functions as a DPST switch. The DPST switch will enable and disable current flow in both buses of the heat- tracing cable.
  • Page 2 Fax: +1.650.474.7711 thermal.info@pentair.com Pentair, DigiTrace and AMC are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice. © 2001-2013 Pentair. PN D55692-000 THERMAL MANAGEMENT SOLUTIONS EN-DigiTraceAMC2B2-IM-H56910      01/13...