4.5 in. (114 mm)
4.0 in. (102 mm)
8.0 in.
(202 mm)
Removable knob cover
Terminal
block
3⁄4 in. NPT conduit entry
WARNING:
This component is an electrical device. It must be installed
correctly to ensure proper operation and to prevent shock or
fire. Read these important warnings and carefully follow all the
installation instructions.
THERMAL MANAGEMENT SOLUTIONS
E507S-LS
Ø.28 in. (7 mm)
mounting hole
(4X)
4.0 in.
(102 mm)
4.5 in.
(114 mm)
6.6 in.
(168 mm)
Adjusting knob
4.0 in. (102 mm)
1.2 in. (30 mm)
0.3 in. (9 mm)
2.0 in.
(50 mm)
Component approvals and performance are based on the use of
specified parts only. Do not use substitute parts or vinyl electrical
tape to make connections.
EN-DigiTraceE507SLS-IM-H56913      01/13
DESCRIPTION
The E507S-LS thermostat is designed for controlling heat-tracing
systems in hazardous locations. The E507S-LS can be used to
control heat-tracing circuits in a pipe-sensing mode (see Figure 1
on back page), to indicate low-temperature (see Figure 2) or high-
temperature (see Figure 3) alarm conditions, or to control the coil
on a contactor (see Figure 4).
APPROVALS
Hazardous locations
Class I, Div. 1 and 2, Groups B, C, D
Class II, Div. 1 and 2, Groups E, F, G
Class III
SPECIFICATIONS
Enclosure
NEMA 4, 7, 9, lacquer-coated cast-aluminum
housing, stainless-steel hardware
Entries
One 3/4 in. NPT conduit hub
Set point range
25°F to 325°F (–4°C to 163°C)
Sensor exposure
–40°F to 420°F (–40°C to 215°C)
limits
Housing exposure
–40°F to 140°F (–40°C to 60°C)
limits
Switch
SPDT
Electrical rating
22 A at 125/250/480 Vac
Accuracy
±6°F (±3.3°C)
Deadband
2°F to 12°F (1.1°C to 6.7°C) above actuation
temperature
Set point
±3°F (±1.7°C)
repeatability
Sensor type
Fluid-filled (silicone) bulb and 9 ft (2.7 m)
capillary
Sensor material
300 series stainless steel
Connection
Screw terminals, 10–14 AWG (2–5 mm
terminals
2
)
1 / 2

Advertisement

loading

Summary of Contents for Pentair Digitrace E507S-LS

  • Page 1 E507S-LS LINE-SENSING THERMOSTAT FOR HAZARDOUS LOCATIONS INSTALLATION INSTRUCTIONS DESCRIPTION The E507S-LS thermostat is designed for controlling heat-tracing systems in hazardous locations. The E507S-LS can be used to control heat-tracing circuits in a pipe-sensing mode (see Figure 1 on back page), to indicate low-temperature (see Figure 2) or high- temperature (see Figure 3) alarm conditions, or to control the coil on a contactor (see Figure 4).
  • Page 2 Fax: +1.650.474.7711 thermal.info@pentair.com Pentair and DigiTrace are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice. © 2001-2013 Pentair. PN 137863 EN-DigiTraceE507SLS-IM-H56913      01/13...