Auxiliary Supply - Honeywell CD3200 User Manual

Thyristor unit, up to 110a
Table of Contents

Advertisement

Honeywell

6.2 Auxiliary supply

Warning: this procedure can be done just by specialized personnel.
To change auxiliary supply voltage sold the correct link-jumper on main PCB
Main PCB
If the Auxiliary Voltage (written on the identification label) is different from Supply Voltage
(to the load ), use an external transformer.
If load voltage is not included in range of 230V ±15% or 460V +15% provide an external
transformer with primary equal to load voltage and secondary 230V if your unit is setted to
230V.
www.honeywell.com/imc
CD3200 up to110A
J9
J10
J11
20
230V Auxiliary supply
J9
J11
460V Auxiliary supply
J9
J11
User's Manual ver. 2.0
J10
J10