Nozzle Arrangement 14Sc - York YPC Engineering Manual

Two-stage steam-fired absorption chiller style d
Table of Contents

Advertisement

Nozzle Arrangement 14SC

STEAM INLET
TOWER WATER NOZZLE ARRANGEMENTS
NO. OF ABS.
NOZZLE
PASSES
ARRANGEMENT
C1
1,3
C2
C3
2
C4
YPC-ST
14SC
*Number of passes refers to the number of absorber passes only. The condenser is always one pass with nozzle sizes that match the absorber.
NOTES:
1.
Choose desired nozzle arrangement – water boxes are not interchangeable.
2.
Standard water nozzles are furnished as welding stub-outs with Victualic grooves, allowing the option of welding, flanges, or the use of Victualic
couplings. Factory installed, class 150 (ANSI B16.5, round slip on, forged carbon steel with 1/16" raised face), water flanged nozzles are optional.
Companion flanges, nuts, bolts, and gaskets are not furnished.
3.
Connected piping should allow for removal of compact water box for tube access and cleaning.
4.
Tower water must enter the absorber first for proper performance.
18
ABSORB. (IN)
COND. (OUT)
E
F
H
G
E
G
H
F
NOZZLE SIZES
EVAPORATOR
2
3
6"
6"
OPPOSITE END
EVAPORATOR NOZZLE ARRANGEMENTS
NOZZLE
NO. OF PASSES
ARRANGEMENT
E1
3
E4
E5
2,4
E7
NUMBER OF PASSES
4
1*
4"
6"
FORM 155.19-EG3 (1011)
(IN)
A
C
A
C
ABS./COND.
2*
3*
6"
4"
JOHNSON CONTROLS
(OUT)
D
B
B
D

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents