AFFINITY SERIES OUTDOOR PACKAGED HEAT PUMP INSTALLATION MANUAL
Auxiliary Heat Ratings
KW
Model
208V
230V
EAM5*
3.6
4.8
EAM8*
5.7
7.6
EAM10*
7.2
9.6
EAL10*
7.2
9.6
EAL15*
10.8
14.4
EAL20*
14.4
19.2
Air flow level for auxiliary heat (Aux) must be equal to or above the minimum CFM in this table
Auxiliary Heat Electrical Data
Heater Amps
Supply
Model
Circuit
208 V
EAM5*
Single
17.3
EAM8*
Single
27.5
EAM10*
Single
34.7
EAL10*
Single
34.7
Single
52.0
EAL15*
L1/L2
34.7
L3/L4
17.3
Single
69.3
EAL20*
L1/L2
34.7
L3/L4
34.7
All heaters rated single phase 60 cycle and include unit fan load
All fuses type "D" time delay (or HACR circuit breaker in USA)
Supply wire size to be determined by local codes
BTU/HR
Stages
208V
230V
1
12,300
16,300
2
19,400
25,900
2
24,600
32,700
2
24,600
32,700
2
36,900
49,100
2
49,200
65,500
Min Circuit Amp
240 V
208 V
240 V
20.0
26.7
30.0
31.7
39.3
44.6
40.0
48.3
55.0
40.0
53.3
60.0
60.0
75.0
85.0
40.0
53.3
60.0
20.0
21.7
25.0
80.0
96.7
110.0
40.0
53.3
60.0
40.0
43.3
50.0
Min
Model Size Compatibility
CFM
026
036 - 042
450
550
650
1100
1250
1500
Fuse (USA)
208 V
240 V
208 V
30
30
40
45
50
60
60
60
80
90
60
60
25
25
100
110
100
60
60
45
50
14
049 - 072
7/9/2017
Fuse (CAN)
CKT BRK
240 V
208 V
30
30
30
40
45
40
50
60
50
60
60
60
80
90
70
60
60
60
25
25
20
110
100
60
60
60
45
50
40
240 V
30
45
60
60
100
60
30
100
60
50
7/9/2017