Mtl5544/Mtl5544S - Repeater Power Supply - Eaton MTL5501-SR Instruction Manual

Crouse-hinds series mtl5500 range isolating interface units
Hide thumbs Also See for MTL5501-SR:
Table of Contents

Advertisement

6 .4 .3

MTL5544/MTL5544S - Repeater Power Supply

Two channel, for 4/20mA HART® for 2- or 3-wire transmitters
The MTL5544 provides fully-floating dc supplies for energising two conventional 2-wire or
3-wire 4/20mA or HART transmitters located in a hazardous area, and repeats the current in
other circuits to drive two safe-area loads. For HART transmitters, the unit allows bi-directional
transmission of digital communication signals superimposed on the 4/20mA loop current.
Alternatively, the MTL5544S acts as a current sink for a safe-area connection rather than driving
a current into the load. Separately powered current sources, such as 4-wire transmitters, can
be connected but will not support HART communication.
MTL5544
PWR
MTL5544S
PWR
Figure 6 .22:
Top labels
for MTL5544
& MTL5544S
The MTL5544 or MTL5544S
can also be used to drive two
safe-area loads from a single
2-wire transmitter (i.e. 1 in,
2 out) by interconnecting the
input channels as shown in
the diagram (right).
Note: In this mode the HART
data is transferred via channel
1 output only.
See also the MTL5544D.
INM 5500 Rev 10
Hazardous area
Safe area
Ch 2
Com
6
Tx+
5
Input
4
4/20mA
Com
3
Tx+
2
Input
1
4/20mA
Ch 1
Terminal
Function
1
Ch1 current input
2
Ch1 transmitter supply +ve
3
Ch1 common
4
Ch2 current input
5
Ch2 transmitter supply +ve
6
Ch2 common
7
Ch2 output +ve via 220Ω for HART apps.
8
Ch2 output –ve (+ve current sink)
9
Ch2 output +ve (–ve current sink)
10
Ch1 output +ve via 220Ω for HART apps.
11
Ch1 output –ve (+ve current sink)
12
Ch1 output +ve (–ve current sink)
13
Supply –ve
14
Supply +ve
MTL5544
MTL5544S
Ch 2
7
I
8
4/20mA
9
I
+
Load
Load
Ch 1
10
I
11
4/20mA
12
I
+
Load
Load
13
Vs–
Vs+
14
20 to 35V dc
Safe area
Hazardous
area
6
I
5
4/20mA
4
3
I
2
+
1
+
+
MTL5544
MTL5544S
Load
Ch 2
7
+
8
4/20mA
9
I
+
Load
Load
Ch 1
10
+
11
4/20mA
12
I
+
Load
Vs–
13
14
Vs+
20 to 35V dc