Mtl5501-Sr - Fail-Safe Switch/Proximity Detector Interface - Eaton MTL5501-SR Instruction Manual

Crouse-hinds series mtl5500 range isolating interface units
Hide thumbs Also See for MTL5501-SR:
Table of Contents

Advertisement

6 .1 .3
Single channel, fail-safe module with line-fault detection
The MTL5501-SR enables a fail-safe switch/proximity detector located in the hazardous area
to control an isolated fail-safe electronic output. It provides line-fault detection (LFD) alarm
contacts and is designed for use with approved fail-safe sensors in loops that require operation
up to SIL3 according to the functional safety standard IEC 61508.
Note: For reliable, long-term operation the load on the LFD switching relay should be not less
than 50mW, e.g. 10mA at 5V DC.
LFD
O/P
MTL5501-SR
PWR
Figure 6 .2:
Top label for
MTL5501-SR
Correct operation of the fail-safe output and LFD is indicated by the LEDs on the front of the
unit. The yellow O/P LED is ON when the fail-safe output is energised. The red LFD LED flashes
if a line fault is detected. The fail-safe output is de-energised (OFF) if the module detects an
incorrect sensor current, an open circuit or a short circuit in the sensor circuit.
Input signal sensors may be either suitable proximity sensors or switches. The proximity sensor
properties are specified in the standard EN60947-5-6:2001; however, when used with
MTL5501-SR modules, additional requirements for the "low-impedance" current of 3.4
±0.5mA must be met. The list below shows suitable proximity sensors, all manufactured by
Pepperl+Fuchs Group, Germany, and specified as usable to SIL3, according to IEC 61508:
SJ 2-SN
SJ 3,5-SN
SJ 3,5-S1N
NJ 2-11-SN
NJ 2-11-SN-G
NJ 2-12GK-SN
20

MTL5501-SR - Fail-safe Switch/Proximity detector interface

Hazardous area
Resistors must
always be fitted
for switch inputs
1k4Ω
10kΩ
Terminal
Function
1
Input –ve
2
Input +ve
7
Output –ve
8
Output +ve
10
LFD
11
LFD
13
Supply –ve
14
Supply +ve
Input / output characteristics
Input value in
sensor circuits
2.9mA < Is < 3.9mA
Is < 1.9mA & Is > 5.1mA
Is < 50µA
Rs < 100Ω
NJ 4-12GK-SN
NJ 5-18GK-SN
NJ 8-18GK-SN
NJ 6-22-SN
NJ 6-22-SN-G
NJ 5-30GK-S1N
Safe area
6
7
5
8
4
9
10
3
+
11
2
12
1
13
14
Fail–safe
Operation
output
ON
Normal
OFF
Normal
OFF
Broken line
OFF
Shorted line
NJ 10-30GK-SN
NJ 15-30GK-SN
NJ 6S1+U1+N
NJ 15S+U1+N
NJ 20S+U1+N
NJ 40-FP-SN-P1
Failsafe
+
output
LFD
Vs–
Vs+
20 to 35V dc
LFD
contacts
CLOSED
CLOSED
OPEN
OPEN
INM 5500 Rev 10