6 .1 .9

MTL5517 - Switch/Proximity detector interface

Two channel, with line-fault detection and phase reversal
The MTL5517 enables two safe-area loads to be controlled, through a relay, by switches or
proximity detectors located in a hazardous-area. When selected, the line-fault detect (LFD) is
signalled through a separate relay and indicated on the top of the module. Line-Fault Detect
and Phase Reversal for the channel are selected by DIL switches on the side of the module
and output is provided by the relay contacts.
See page 19 for LFD and PR switch details. Channel 1 & 2 switch settings apply.
For switch sensor inputs, with LFD selected, make sure resistors (22kΩ and 680Ω) are fitted.
Note: For reliable, long-term operation the load on the output switching relays should be not less
than 50mW, e.g. 10mA at 5V DC.
Hazardous area
LFD
CH2
STS
LFD
CH1
STS
MTL5517
PWR
Switch-type sensors
require resistors
if LFD is selected
Figure 6 .9:
Top label
for MTL5517
INM 5500 Rev 10
Safe area
680Ω
6
+
22kΩ
5
4
680Ω
3
+
2
1
22kΩ
Terminal
Function
1
Input –ve (Ch 1)
2
Input +ve (Ch 1)
4
Input –ve (Ch 2)
5
Input +ve (Ch 2)
7
Line-fault detection
8
Output (Ch 2)
9
Output (Ch 2)
10
Line-fault detection
11
Output (Ch 1)
12
Output (Ch 1)
13
Supply –ve
14
Supply +ve
LFD
7
LFD
8
Ch 2
9
LFD
10
11
Ch 1
12
13
Vs–
Vs+
14
20 to 35V dc