IMI CORNELIUS INC g One Cornelius Place g Anoka, MN 55303-6234 Telephone (800) 238-3600 Facsimile (612) 422-3246 Service Manual SELF-CONTAINED FLAKED ICE MAKER Model: Series 200, 525, 725 (R404A Refrigerant) IMPORTANT: TO THE INSTALLER. It is the responsibility of the Installer to ensure that...
When writing, please state the model and serial number of the machine. Address all correspondence to: A Product of IMI Cornelius Inc. One Cornelius Place Anoka, MN 55303- -6234 Phone 800- -554- -3526...
6-IN. 15-CM A- 1/4 WATER INLETS (S.A.E. MALE FLARE) B- 5/8 O.D. TUBE (DRAIN) C- 1/2 O.D. TUBE (DRAIN) FIGURE 1. 200 SERIES SPECIFICATIONS ICE PRODUCTION CAPACITY (approximate) AF-200-P(S)-SCR PRODUCTION CHART AIR TEMPERATURE WATER TEMPERATURE 50° F/10° C 70° F/21° C 80°...
INSTALLATION INSTRUCTIONS You will get better service from the ice machine, longer life and greater convenience if you choose its location with care. Here are a few points to consider: 1. Select a location as close as possible to where you are going to use the ice. 2.
Connect a drain hose to the condensate drain stub tube. NOTE: All plumbing must be done in accordance with national and local codes. Connect the electrical supply line to the unit. NOTE: Make sure the proper voltage and number of wires are provided. See serial plate for this in- formation.
TYPICAL WATER CIRCUIT The supply water enters the float chamber through a small orifice. The water level rises and lifts the buoyant float with it. The float attached to the float arm seats a valve to shut off any further water supply. As water leaves the float chamber, the level drops along with the float and arm, causing the valve to open and admit more water.
TYPICAL REFRIGERANT CIRCUIT Heat always flows from hot to cold and therefore, the ” heat load”supplied to the evaporator section by water gives up its heat to the refrigerant which is at a temperature below the freezing point of water. This refrigerant now passes through the heat exchanger back to the compressor, as a low pressure vapor.
ELECTRICAL CIRCUIT CIRCUIT DESCRIPTION As the manual on--off circuit breaker switch is pushed to ” on” , an electrical circuit is completed to the gearmotor via the circuit breaker gearmotor overload, power relay/contactor, gearmotor delay thermostat and the bin ther- mostat.
COMPRESSOR START RELAY This is a current type relay and contains a N.O. contact which is connected in series with the start winding of the compressor. The relay coil is electrically in series with the run winding. When power is applied, the compressor draws high current which sets up a magnetic field in the magnet coil which causes the relay to operate, closing the relay contact.
MAINTENANCE THE FOLLOWING MAINTENANCE SHOULD BE PERFORMED AT LEAST EVERY SIX MONTHS ON FLAKED ICE MACHINES: 1. Check power supply with machine running for proper voltage. 2. Check water level in the float tank reservoir. Water level should be maintained at the top of the evaporator. Adjust if necessary.
IMI Cornelius has water filter/treatment systems available to control imputities found in your water supply. Con- tact your local dealer for more information.
WINTER STORAGE If the unit is to be stored in an area where the temperature will drop below freezing, it is most important that all water lines be drained to prevent them from freezing and possible rupture. To blow out the water line, disconnect the water supply at the cabinet inlet and use air pressure to force the wa- ter into the water reservoir pan.
ON- - OFF SWITCH CIRCUIT BREAKER RATED 1.5 AMPS GEAR MOTOR START RELAY DELAY GEAR THERMOSTAT MOTOR GEAR MOTOR THERMOSTAT START CAPACITOR FAN MOTOR WIRE NUT FAN SWITCH CONTROL HIGH PRESSURE COMPRESSOR COMPRESSOR OVERLOAD COMPRESSOR START CAPACITOR 43- - 52 MFD 330 V COMPRESSOR START RELAY CONTACTOR...
SERVICE ANALYSIS Trouble Probable Cause Remedy UNIT WILL NOT RUN On--off switch in ” off”position. Turn switch to ” on” . Defective on--off switch. Check and replace. Blown fuse. Replace fuse and check for cause of blown fuse. Thermostat set too warm for Adjust colder.
Trouble Probable Cause Remedy WATER LEAKS. Worn or bad float valve Check and replace Float and arm assembly stuck Check and replace ” O”ring leaking at bottom of Check and replace evaporator shell Storage bin drain and tubing Check and repair EXCESSIVE NOISE OR Mineral or scale deposits on Remove and clean inside...
Trouble Probable Cause Remedy UNIT GOES OFF ON RESET. Plugged expansion valve, Check back pressure, replace (CONT’ D) causing low back pressure valve, evacuate and re--charge system, replace drier--strainer Slight leak, causing low back Check back pressure, find gas pressure leak, repair leak, evacuate system, add drier and recharge Loose hold--down assy...
CORNELIUS whichever time period elapses first. The obligation of CORNELIUS under this warranty is limited to repair or replacement (at the option of CORNELIUS) FOB factory in Mason City, Iowa of the part (or Parts) of any Machine that is proven defective.