5 Control system
Standard control functions

5.4.3 Activation for protection device control

Operation
Excessively high
drain water level
on RU
Excessively high
drain water level
on IU
Excessively high
temperature of IU
fan motor
Overcurrent (>5A) to
control circuit
Overcurrent to MC
Excessively high
discharge gas
temperature
High pressure
4.15 MPa
High temperature of
inverter fin
High temperature of
RASC unit fan
Overcurrent (>5A) to
control circuit
IU: Indoor unit
RU: RASC unit
91
SMGB0091 rev.2 - 11/2015
B
FS: Open contact
Power to H2: OFF
Activation of IU PCB
A
protection device
ITI: open
Blown fuse
Power to IU
EFR1 on IU
transformer: OFF
A
Blown fuse
EF1, EF2
Activation of RU
B
PCB protection
device
PSH: Open contact
Y52C: OFF
CMC: OFF
ITO: Open
Blown fuse
A
EFR1 on RU
YH2: Closed contact
MD: ON
B
"RUN" light flickers
MIF: stop
Light and LCD are
not indicated
B
A
MC: OFF
MOF: OFF
5