Safety And Control Device Setting - Hitachi RUA-NP5ATS Instruction Manual

Hide thumbs Also See for RUA-NP5ATS:
Table of Contents

Advertisement

6.5 Safety and Control Device Setting

Model
For Compressor
High Pressure Switch
Cut-Out
Cut-In
Overcurrent Relay
230V, 60Hz
Internal Thermostat
Cut-Out
Cut-In
CCP Timer for Compressor
(built-in PCB)
No. 1
No. 2
For Evaporator Fan Motor
Overcurrent Relay
For Condenser Fan Motor
Internal Thermostat
Cut-Out
Cut-In
For Control Circuit Fuse
Capacity
Table 3. Safety and Control Device Setting
RUA-NP5ATS
E505DH
MPa
4.15
2
kg/cm
G
42.3
MPa
3.2
2
kg/cm
G
32.6
A
21
°C
130
°C
108
min
3
min
---
A
2.6
°C
160
°C
130
A
2.5
RUA-NP8ATS
RUA-NP10ATS
E855DH
E505DH
Automatic Reset, Non-Adjustable
4.15
4.15
42.3
42.3
3.2
3.2
32.6
32.6
Automatic Reset, Non-Adjustable
36
25
Automatic Reset, Non-Adjustable
130
130
108
108
Non-Adjustable
3
3
---
---
3.6
6.0
Automatic Reset, Non-Adjustable
160
160
130
130
2.5
2.5
TEST RUNNING
RUA-NP15ATS
E855DH
4.15
42.3
3.2
32.6
39
130
108
3
---
9.0
160
130
2.5
9

Advertisement