11 Maintenance notes
Service and maintenance record
11.3 Service and maintenance record
No.
Check item
1
Is the service area sufficient?
2
Is there a short circuit of the discharged air?
3
Any heat influence?
4
Is the ground wire connected?
5
Refrigerant piping
6
Fixing the units
Is there any damage on the outer surface or the
7
internal surface?
8
Checking the screw and the bolts
9
Tightening the terminal screws
10
Are the compressor terminals tightly fixed?
11
Insulation resistance
12
Does the drain water flow smoothly?
13
Check for a leakage in the compressor
14
Check for a leakage in the RASC heat exchanger
15
Check for a leakage in the indoor heat exchanger
16
Check for a leakage in the 4-way valve
17
Check for a leakage in the check valve
18
Check for a leakage in the accumulator
19
Check for a leakage in the strainer
20
Check for a leakage in the electronic expansion valve ditto
21
Check for a leakage in the piping
22
Check the direction of the fans
23
Voltage among each phase
24
Vibration and sound
25
Activation of each operation mode
26
High-pressure cut-out switch
27
Check the activation of the drain-up mechanism.
28
Air inlet temperature of the indoor unit DB/WB
29
Air outlet temperature of the indoor unit DB/WB
30
Air inlet temperature of the RASC unit DB/WB
31
Air outlet temperature of the RASC unit DB/WB
32
High-pressure switch
33
Low-pressure switch
34
Operating voltage
35
Operating current
36
Instructions to the client for cleaning the air filter
37
Instructions to the client about the cleaning method
38
Instructions to the client about the operation
288
SMGB0091 rev.2 - 11/2015
Action
-
-
-
-
-
-
-
Tighten if loosened.
Tighten all the terminal screws with a
Phillips screwdriver.
Push all the terminals.
Measure the insulation resistance with an
insulation resistance meter.
Compressor and fan motor: greater than
3MΩ
Others: greater than 3MΩ
Check the smooth flow by pouring some 
water.
Check for any leakage.
ditto
ditto
ditto
ditto
ditto
ditto
ditto
By viewing the airflow volume
Higher than AC220V
Check the fan, the compressor, the
piping, and others.
Check the activation of the COOL switch, 
the HEAT switch, the STOP switch and 
the TEMP switch.
Check the actual activation value.
Check the activation during the cooling 
process.
-
-
-
-
-
-
-
-
-
-
-
Judgement
Yes
No
Yes
No
Yes
No
Yes
No
Good
Not good
Good
Not good
Yes
No
Tightened
Not tightened
Tightened
Not tightened
Pushed
Not pushed
Good
Not good
Good
Not good
Good
Not good
Good
Not good
Good
Not good
Good
Not good
Good
Not good
Good
Not good
Good
Not good
Good
Not good
Good
Not good
Good
Not good
Good
Not good
Good
Not good
Good
Not good
Good
Not good
Good
Not good
(°C)DB
(°C)WB
(°C)DB
(°C)WB
(°C)DB
(°C)WB
(°C)DB
(°C)WB
kg/cm²G
kg/cm²G
V
A
Done
Not yet
Done
Not yet
Done
Not yet