3 Piping work and refrigerant charge

Drainage and drain pipe installation

3.7 Drainage and drain pipe installation

Provision regarding installation place
Drain water sometimes turns to ice. Therefore, avoid draining in a transited area, since it may become slippery.
Install the unit making sure that the drain outlet part is lower (>25mm / <30mm) than the opposite side in order to avoid
incorrect drain discharge.
Floor mounted
Drain pipe

Drain pipe location
Drain pipe location is indicated in the figures below:
RASC-(4-6)HNPE
Drain pipe
(30 mm Outer diameter)

Drain pipe connection
It is mandatory to connect a siphon as shown in the figure below. Pay special attention when connecting it to the
unit (proper installation work is needed in order to guarantee matching of connection pipes).
Slope >2%
Fasten the siphon to the drain hose with an adhesive and a field-supplied clamp.
Prepare a draining pipe with an internal diameter higher than 30 mm for the draining line which shall be bent with a
down slope > 2 %.
Check to ensure that the water drains smoothly by pouring some water into the drain pan.
Check to ensure that the water does not remain in the drain pan.
Check the drain connections periodically (once a year), to avoid occurrence of water leakage.
!
C A U T I O N
If the unit is installed in a cold area, the drain water may freeze. Install an electric heater (field-supplied) at the drain connection.
Do not install the unit using vibration-proof springs or mounting springs.
57
SMGB0091 rev.2 - 11/2015
>25mm
<30mm
>75 mm
Plug
Ceiling suspended
>25mm
<30mm
Drain pipe
RASC-(8/10)HNPE
Drain pipe (x2 locations)
(30 mm Outer diameter)