Samsung AD18B1C09 Owner's Instructions & Installation Manual page 32

Multi-split type room air conditioner ( cool and heat )
Hide thumbs Also See for AD18B1C09:
Table of Contents

Advertisement

P
I
REPARING THE
NSTALLATION
Deciding on Where to Install the Air Conditioner (cont.)
26,000Btu/h
Indoor unit
AD26B1C13
Respect the clearances and maximum lengths indicated in the diagram below when installing the unit.
100 mm
(4 inch)
or more
300 mm
(12 inch)
minimum
600 mm
(24 inch)
minimum
INDOOR UNIT
A
B
OUTDOOR UNIT
32
E-
Power supply
Outdoor unit
Ø, V, Hz
UD26B1C2
1,208-230~,60
25 mm (1 inch)
or more
A-unit
12,500 Btu/h
600 mm (24 inch)
minimum
300 mm
(12 inch)
minimum
A
B
Circuit breaker
(20A)
Piping length and the height.
Unit
A-unit
B-unit
B-unit
12,500 Btu/h
160 mm
(6 inch)
or more
A
(15 m (49ft. 3in)
maximum)
Main power switch
Pipe size
MAX. piping length
Liquid
GAS
A
"
15 m (49ft. 3in)
1/4
1/2
"
"
15 m (49ft. 3in)
1/4
"
1/2
B
(7 m (23ft) maximum)
MAX. height
B
7 m (23ft)
7 m (23ft)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ad26b1e3Ad26b1c13Ud18b1c2Ud26b1c2Am26b1(b2)c13

Table of Contents