4 Planning

4.1
4.2
Building Technologies
Fire Safety

Compatibility

Compatible with fire control panels that support the FDnet/C-NET detector line.
You will find detailed information in the 'List of compatibility'.
The table below shows the compatibility of the aspirating smoke detectors and
installed communication transponder FDCC221S with various fire control panels:
Detector line
FC20xx
FDnet
C-NET
X = compatible
– = not compatible
Please also observe the documentation for your fire detection system.
See also
 Applicable documents [➙ 9]

Operating modes

Three different modes can be set.
'Automatic: switches between blue and blue-red based on ratio'
This mode is suitable for standard use. The sensitivity to small smoke particles is
high and dust suppression is normal. The particle size is taken into account. This
reduces the likelihood of a false alarm.
'Robust'
This mode is suitable for use in dirty rooms where there is a high dust load. The
sensitivity to small smoke particles is lower, but this results in a higher level of dust
suppression. This makes use possible in a dirty environment or in changing
ambient conditions.
'Ultra sense: always blue'
This mode is suitable for use in clean rooms where there is a low dust load. The
sensitivity to small smoke particles is very high and dust suppression is low. As a
result, the detector is very sensitive even to minor changes relating to smoke or
dust in the intake air.
Parameter sets can be used to make further settings with a view to fine-tuning the
product for the installed pipe system. When making your selection, take the
following into account:
Ambient conditions
Place of installation
Usage conditions
Alarm delay
In the FDnet/C-NET, the operating mode and parameter sets can be configured
from the fire control panel.
To determine suitable parameters, use the recommendations from the
'FXS2055 A6V10340094' software.
Fire control panel
FC72x
X
X
Planning
Compatibility
SIGMASYS
AlgoRex
A6V10334410_h_en_--
2015-09-29
4
39