Installation Checklist; Clearances To Combustibles; Locating Your Regency Gas Stove; Combustion And Ventilation Air - Regency FG39-NG2 Owners & Installation Manual

Freestanding gas stove
Hide thumbs Also See for FG39-NG2:
Table of Contents

Advertisement

11. Under no circumstances should this ap-
pliance be modified. Parts that have to be
removed for servicing should be replaced
prior to operating this appliance.
12. Installation and any repairs to this appliance
should be done by an authorised service
person. An authorised service person should
be called to inspect this appliance annually.
Make it a practice to have all of your gas
appliances checked annually.
13. Do not slam shut or strike the glass door.
14. Under no circumstances should any solid
fuels (wood, paper, cardboard, coal, etc.)
be used in this appliance.
15. The appliance area must be kept clear and
free of combustible materials, (gases and
other flammable vapours and liquids).
INSTALLATION
CHECKLIST
1. Check Clearances to Combustibles, location
of unit and flueing requirements.
2. Install Louvers.
3. Install flueing, either with the DV Stove Hori-
zontal Flue Kit or the Dura-Flue Termination
kits. Set Flue Restrictors.
4. Make gas connections. Test the pilot. Must
be as per diagram.
5. If necessary, convert to LPG or convert to
lower BTU rating.
6. Test Gas Pressure.
7. Install log set.
8. Install Front Door Front.
9. Install optional Remote Control.
10. Final check.
Before leaving this unit with the customer, the
installer must ensure that the appliance is fir-
ing correctly and operation fully explained
to customer.
This includes:
1) Clocking the appliance to ensure the correct
firing rate (rate noted on label) after burning
appliance for 15 minutes.
2) If required, adjusting the aeration to ensure
that the flame does not carbon. First allow
the unit to burn for 15-20 min. to stabilize.
FG39-2 Freestanding Gas Stove
CAUTION: Any alteration to the product that
causes sooting or carboning that results
in damage is not the responsibility of the
manufacturer.
CLEARANCES TO
COMBUSTIBLES
The clearances listed are MINIMUM distances.
Measure the clearance to both the appliance and
the chimney connector. The farthest distance is
correct if the two clearances do not coincide.
For example, if the appliance is set as indicated
in one of the figures but the connector is too
close, move the stove until the correct clearance
to the connector is obtained.
This appliance may be installed only with the
clearances as shown in the situations pictured.
Do not combine clearances from one type of
installation with another in order to achieve
closer clearances.
This unit can be installed on a solid combustible
surface like a wood floor. This unit can also be
installed directly on carpeting or vinyl when
the bottom pedestal cover plate (provided with
unit) is installed.
Use the minimum clearances shown in the
diagrams below:
CLEARANCES
A Side Wall to Unit
B Back Wall to Unit
E Side Wall to Unit
C Back Wall to Flue Centerline 280 mm
D Side Wall to Flue Centerline 521 mm
F Side Wall to Flue Centerline 280 mm
Minimum ceiling height is 914 mm from top
Minimum ceiling height is
914 mm from top of unit.
LOCATING YOUR
REGENCY GAS STOVE
When selecting a location for your stove, en-
sure that the clearances listed above are met
as well as ensuring that there is adequate ac-
cessibility for servicing and proper operation.
A) Cross Corner
B) Room Divider
C) Island
D) Flat on Wall
E) Flat on Wall Corner
F) Flush with Wall/ Alcove
For Flue Termination requirements, see page 9.
190 mm
150 mm
A
50 mm
F
E
COMBUSTION AND
VENTILATION AIR
The combustion air from this appliance is drawn
from outside the building through the outer flue.
Extra provision for combustion air inside the
room is not required.
installation
3.7
Max.
B
3.7
Max.
C
D
7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fg39-lpg2Firegenie fg39-ng2Firegenie fg39-lpg2

Table of Contents