Bfm #44 (Ch1) And Bfm #63 (Ch2): Setting Change Ratio Limiter - Mitsubishi Electric MELSEC FX2N-2LC User Manual

Temperature control block
Hide thumbs Also See for MELSEC FX2N-2LC:
Table of Contents

Advertisement

FX2N-2LC Temperature Control Block
7.2.27

BFM #44 (CH1) and BFM #63 (CH2): Setting change ratio limiter

In BFM #44, set the setting change ratio limiter of CH1. In BFM #63, set the setting change
ratio limiter of CH2.
The setting change ratio limiter function changes step by step the difference in the temperature
set value when the temperature set value is changed.
Set the variation (%) per minute.
The allowable set range is from 0.1 to 100.0%.
When BFM #44/#63 is set to "0", the setting change ratio limiter function is disabled and the
set value immediately changes.
Example
When the temperature set value 1 (SV1) is changed to the temperature set value 2 (SV2)
(When the set value is changed to a larger value)
SV2
SV2
The set value is
changed.
- When the power is turned on, the PV changes to the SV step by step if the change ratio
limiter function is used. (When the setting change ratio limiter function is used.)
- When the alarm function is used, the alarm wait function is not performed while the PV is
changing to the SV step by step.
SV
Set by how many percentages
of the span the set value is to
increase in a minute.
SV
0.0 to
100.0%
of span
1 min
Buffer Memory (BFM) 7
7-17
7