FX2N-2LC Temperature Control Block
7.2.21
BFM #37 (CH1) and BFM #56 (CH2): Output limiter upper limit
BFM #38 (CH1) and BFM #57 (CH2): Output limiter lower limit
In BFM #37 and BFM #56, set the output limiter upper limit of CH1 and CH2 respectively. In
BFM #38 and BFM #57, set the output limiter lower limit of CH1 and CH2 respectively.
Use these BFMs when setting the upper limit and the lower limit for the setting of the control
output value (MV) (BFM #5, BFM #6).
The allowable set range of the upper limit is from the output limiter lower limit to +105%. The
allowable set range of the lower limit is from -5.0% to the output limiter upper limit.
Output limiter
(upper limit)
Output limiter
(lower limit)
- While the output limiter is effective, proper PID constants may not be obtained during
auto tuning.
It is recommended not to use the output limiter when auto tuning is used.
- While two-position control is used, the output limiter is not effective.
100%
MV
0%
Buffer Memory (BFM) 7
7-12