Toshiba RAV-RM301SDT-E Service Manual page 67

Air-conditioner (split type). slim duct type
Hide thumbs Also See for RAV-RM301SDT-E:
Table of Contents

Advertisement

Table 1. Setting data (CODE No. table (example))
CODE No. (DN)
01
Filter sign lighting time
02
Filter pollution level
03
Central control address
06
Heating suction temperature shift
0F
Cooling only
10
Type
11
Indoor unit capacity
12
System address
13
Indoor unit address
14
Group address
Temperature range of cooling/heating
1E
automatic SW control point
28
Power failure automatic recovery
2b
Thermostat output SW (T10
31
Ventilation fan (standalone)
32
Sensor SW (Selection of static pressure)
5d
External static pressure
60
Timer setting (wired remote controller)
77
Dual set point
8b
Connection of high heat feeling
Demand setting
C2
(outdoor unit current demand)
d0
Remote controller operation save function
d1
Frost protection function
Table 2. Type: CODE No. 10
Setting data
0001∗1
4-way Cassette Type
0005∗2
Slim Duct Type
∗1 EEPROM initial value on the P.C. board for indoor unit
servicing.
CAUTION
∗2
For above models, set the CODE No. to "
0000
setting data "
Table 4.
External static pressure settings CODE No.5d
Be sure to set up a tap change based upon the resistance (external static pressure) of the duct to be connected
Setup data
External static pressure
0000
0001
0003
0006
The list above is when SW501-1 and SW501-2 is OFF.
* Include standard filter pressure loss.
Item
)
Type
Type name abb.
RAV-GM∗∗∗UT∗
RAV-RM∗∗∗SDT∗
CE
0001
" (initial) to "
".
10Pa*
20Pa*
30Pa*
50Pa*
Setting data
Depending on Type
0000: standard
0099: Not determined
0002: +2 ˚C
0000: Heat pump
Depending on model type
Depending on capacity type
0099: Not determined
0099: Not determined
0099: Not determined
0003: 3 deg (Ts ±1.5)
0000: None
0000: Thermostat ON
0000: Not available
0000: Body sensor
0000: 10Pa*
0001: 20Pa*
0003: 30Pa* (Factory default)
0006: 50Pa*
* Include standard filter pressure loss.
0000: Available
0000: Unavailable
0000: None
0075: 75 %
0001: Enable
0000: None
Table 3.
Indoor unit capacity: CODE No. 11
Setting data
∗ EEPROM initial value on the P.C. board
" and the
for indoor unit servicing.
– 67 –
Factory-set value
Type
0000∗
Disable
0003
30
0006
40
0009
56
.