Maintenance; Troubleshooting - Greenheck CFSD-211 Installation, Operation And Maintenance Manual

Fire & combination fire smoke dampers (with factory installed sleeve and actuator) vertical and horizontal mount; fsd series; dfd series; dfdtf series; cfsd series; sedfd series; sefsd series; imo series; ssfsd series
Table of Contents

Advertisement

Proprietary Flange System Breakaway Connections
(TDC by Lockformer, TDF by Engle)
TDC and TDF systems are
approved as breakaway
connections when installed as
described in the TDC or TDF
addendum to the SMACNA Duct
Construction. Standard 6 in.
(152mm) metal clip may be used
with spacing as shown in diagram
(see Fig. 15 & 16). 3/8 in. (9.5mm)
metal bolts and nuts may be used to fasten together
corner pieces. (see Fig. 17)
Damper Maintenance
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild
detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and jamb
seals, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust.
Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with:
• The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA 503-03 and local codes.
• Actuator manufacturer recommendations.
Damper Troubleshooting
The following is a possible cause and correction list for common concerns with the dampers.
Symptom
Damper does not fully
open and/or close
RRL or TOR sensor
tripped
Damper does not oper-
ate
8
Sleeve
Sleeve
Typical TDC/TDF joint
Fig. 16
Typical TDC/TDF joint
Possible Cause
Frame is 'racked' causing blades to bind
on jamb seals
Actuator linkage loose
Defective motor
Screws in damper linkage
Contaminants on damper
Heat
No power supplied to the actuator
Clip Spacing
Clip Spacing
Std. Clip
Length
6 in.
6 in.
60 in. Duct
6 in.
4 Req'd.
60 in. Duct
7 in.
4 Req'd.
48 in. Duct
7 in.
3 Req'd.
5 in.
48 in. Duct
36 in. Duct
3 Req'd.
Duct
3 Req'd.
5 in.
36 in. Duct
Duct
24 in. Duct
3 Req'd.
2 Req'd.
18 in. Duct &
24 in. Duct
Smaller
1 Req'd.
2 Req'd.
Duct
18 in. Duct &
Smaller
Fig. 17
1 Req'd.
Fig. 18
Adjust frame such that it is square and plumb
Close damper, disconnect power, adjust and tighten
linkage
Replace
Damper installed too far into wall. Move out to line as
designated on damper label
Clean with a non-oil based solvent (see Damper

Maintenance)

Push reset button located on backside of RRL or TOR
Add power supply
Copyright © 2010 Greenheck Fan Corporation
Std. Clip
Length
9 in.
9 in.
6 in.
6 in.
7 in.
5 in.
5 in.
5 in.
5 in.
5 in.
5 in.
C L
C L
Duct
Duct End
Flange
Corner Piece
Corrective Action
IOM 461336 FSD Rev. 15 October 2010
6 in.
7 in.
3/8 in. bolt
(optional)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents