Requirements Specific To Solid-Walled Cabinets - Cisco MDS 9396T Hardware Installation Manual

Multilayer fabric switch
Hide thumbs Also See for MDS 9396T:
Table of Contents

Advertisement

Cabinet and Rack Installation

Requirements Specific to Solid-Walled Cabinets

In addition to the requirements listed in the
cabinets must meet the following requirements:
• The rack must have a roof-mounted fan tray and an air-cooling scheme in which the fan tray pulls air in
• The front and rear doors, and side panels, must be installed and nonperforated so that air flows predicatably
• The overall cabinet depth should be 36 to 42 in. (91.4 to 106.7 cm) to allow the doors to close and to
• The open area of the floor air intake must be a minimum of 150 sq. in. (968 sq. cm).
• The lowest piece of equipment should be installed at a minimum of 1.75 in. (4.4 cm) above the floor
at the bottom of the cabinet and sends it out from the top, with a minimum airflow of 849.5 m3/h exiting
the cabinet roof through the fan tray, should be available.
from bottom to top.
facilitate adequate airflow.
openings to prevent blocking the floor intake.
General Requirements for Cabinets and Racks
Cisco MDS 9396T Multilayer Fabric Switch Hardware Installation Guide
Requirements Specific to Solid-Walled Cabinets
section, solid-walled
19