Performance Specifications; Alarm Output Specifications - Panasonic AFP7PSA1 User Manual

Cpu unit
Hide thumbs Also See for AFP7PSA1:
Table of Contents

Advertisement

8.2.2 Performance Specifications

Items
Rated input voltage
Input voltage amplitude range
Rated frequency
Frequency range
Phases
Input
Input current
Inrush current
Leakage current
Momentary power drop time
Rated output current (Note 1)
Output
Overcurrent protection (Note 2)
Guaranteed lifetime
Terminal screw
(Note 1) Use the unit within the rated output current.
(Note 2) Oscillation is stopped during protected operation.
To recover, turn off the input and then on again. Wait at least 180 seconds before turning the input on again.

8.2.3 Alarm Output Specifications

Items
Contact capacity
Alarm contact operations
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
100 to 240V AC
85 to 264V AC
50 / 60 Hz
47 to 63 Hz
Single-phase
AFP7PSA1: 0.75A
AFP7PSA2: 1.25A
40 A (0-P) or less; Cold start
0.75 mA or less between AC input and protective earth terminals
10 ms or more
AFP7PSA1: 24V DC, 1A
AFP7PSA2: 24V DC, 1.8A
On
27,000 hours (+55C)
Built-in (Replacement is not available)
1A 30V DC
Contact OFF at CPU alarm occurrence
8.2 Power Supply Unit Specifications
Description
Description
8-25