Pump Capacity; Tailpipe Flow; Figure 15: Vacuum Loss Curve For 4" Shared Tailpipe; Table 2: Pump Capacity - Roberts Gorden CoRayVac CRV-B-2 Design Manual

Custom engineered, gas-fired, low-intensity infrared heating system
Hide thumbs Also See for CoRayVac CRV-B-2:
Table of Contents

Advertisement

CRV-S
D
M
ERIES
ESIGN
ANUAL

5.2 Pump Capacity

The flow unit capacity of the pump is indicated on
Page 14, Table 2, as a function of installed altitude.
When the CRV-Series system is designed in accor-
dance with this set of instructions and is in proper
operating condition, a vacuum from 2-3" w.c. will be
obtainable at each end vent (i.e. at all burners).

Table 2: Pump Capacity

Installed Altitude
Feet Above
Meters Above
Sea Level
Sea Level
'
'
0
- 2000
0 m - 609 m
'
'
2001
- 3000
610 m - 914 m
'
'
3001
- 4000
915 m - 1219 m
'
'
4001
- 5000
1220 m - 1524 m
'
'
5001
- 6000
1525 m - 1828 m
'
'
6001
- 7000
1829 m - 2134 m
'
'
2135 m - 2438 m
7001
- 8000
'
'
2439 m - 2743 m
8001
- 9000
There are a number of design requirements which, if
not met, will reduce the vacuum obtainable and
thereby the effective flow capacity of the pump. These
include:
• Minimum Length of Tailpipe - If less than the
minimum length of tailpipe is provided per radiant
branch, there will be insufficient cooling of the com-
bustion gases and improper operation of the pump.
• Line Loss Check for Tailpipe is applicable to
sections of tailpipe which are common to two or
more radiant branches (i.e. shared lengths). See
Page 14, Figure 15.
• Excessive back pressure on discharge line of
pump can be caused by partial blockage or too
much flow for length. See Section 5.3.1
• More than maximum number of burners or flow
units per radiant branch. See Page 14, Table 2.
• Excessive number of elbow or tee fittings
which increases vacuum loss.

5.3 Tailpipe Flow

Excessive flow loading in a single section of tailpipe
can cause low vacuum and lower effective pump
capacity. For the pump to develop the proper vacuum,
the length of tailpipe must not be excessive for the
14
Maximum Flow Units
EP-200
EP-300
EP-100
Series
Series
66
112
224
63
105
215
60
100
206
57
95
197
54
90
188
51
84
180
48
80
170
45
75
161
number of flow units carried in the tube.
See Figure 15. Readings for length and flow when
plotted on the graph must fall on OK side to avoid
excessive vacuum losses.
FIGURE 15: Vacuum Loss Curve for 4" Shared
Tailpipe
NOTE: For 6" (15 m) tailpipe, length is limited to a
maximum of 100' (30 m). See Page 16, Section 6.3
for more details.
Lengths shown include allowance for 1 elbow every
50' (15 m); deduct 15% of length for each additional
elbow used per 50' (15 m) length.
5.3.1 Pump Exhaust Length Requirements
The tube length on the exhaust side of the pump is
considered excessive if not within the following condi-
tions:

Table 3: Pump Exhaust Requirements

Pump Series
Exhaust Tube Length Exhaust Tube Diameter
EP-100
Up to 25' (7.6 m)
EP-100
Up to 50' (15 m)
EP-200
Up to 10' (3 m)
EP-200
Up to 25' (7.6 m)
EP-200
Up to 50' (15 m)
EP-300
Up to 10' (3 m)
EP-300
Up to 25' (7.6 m)
EP-300
Up to 50' (15 m)
4" 3 Elbows
5" 3 Elbows
4" 0 Elbows
5" 3 Elbows
6" 3 Elbows
6" 1 Elbows
7" 3 Elbows
8" 3 Elbows