Wiring Connection Diagram - Beckett NX50LG Manual

Nx series oil burner
Table of Contents

Advertisement

Start
the
Burner
and Set Combustion
The burner is supplied with either a one-stage
pump or a two-stage pump based on the oil supply
system requirements.
Consult the instructions pro-
vided with the pump for installation specifications.
When installing a one-pipe
system,
connect the
inlet line to the pump inlet. The fuel pump may be
installed with gravity feed or lift. The maximum al-
lowable lift for a single pipe installation is 8 ft.
When installing a two-pipe system,
remove the
1/16" pipe by-pass plug from plastic bag attached
to fuel unit.
Remove 1/4" plug from return port.
Insert and tighten the by-pass plug. Attach return
and inlet lines. The return line should terminate ap-
proximately 3 to 4" above supply line inlet. Failure
to do this may introduce air into the system and
could result in loss of prime.
Wiring
Connections
Diagram
Refer to the appliance
manufacturer's
wiring dia-
gram prior to connecting the burner wiring. All wir-
ing must be in accordance with the latest revision of
National Electric Code NFPA 70 and all local codes
and regulations.
The R7184 primary control with valve-on delay and
burner motor-off delay, shown in Figure 4, requires
a constant 120 volt AC power source supplied to
the black wire on the control. (Refer to the appli-
ance manufacturer's
instructions.)
The red wire
goes to the appliance limit circuit. Please note that
other control manufacturers
may use different wire
colors for power and limit connections.
Figure 4a. - Typical
Burner
Control
Wiring
Refer to the appliance manufacturer's
wiring diagram for actual specifications.
120
VAC
BURNER
START
WIRE
FROM
APPLIANCE
(FROM
LIMIT
CIRCUIT)
LI
(HOT)
120
VAC
/
FROM
L2
(NEUTRAL)
APPLIANCE
EQUIPMENT
GROUND
.4_
GROUND
SCREW
BURNER
JUNCTION
BOX
WHITE
,_<_
WHITE
_<_
WHITE
._<_
WHITE
(<_
VIOLET
BLUE /
WHITE STRIPE
ORANGE
(<
YELLOW
<<
YELLOW
<(
LIMIT
L1
L2
VALVE
IGNITION
MOTOR
CAD
CELL
CAD
CELL
R7184
SERIES
PRIMARY
CONTROL
I
(_- .......
2
(_
//
3T_---
T@-.--
TO
OTHER
ENVIRACOM
TM
ENABLED
DEVICES
---F_"
I
24
VAC
THERMOSTAT
TO REMOTE
LOW VOLTAGE
AC ALARM
CIRCUIT
(IF USED)
SK9359D
_
=
120
VAC
FIELD
WIRING
-
120
VAC
FACTORY
WIRING
-
LOW VOLTAGE FIELD WIRING
-
LOW VOLTAGE FACTORY WIRING
=
WIRE
WITH
1/4"
QUICK
CONNECT
RECEPTACLE
RWB 6104 BNX R02
Page 7