Temperature Controller Installation
Location
The controller should be out of reach of small
children.
Avoid locations where the controller may become
hot (near the oven or radiant heater).
Avoid locations in direct sunlight. The digital
display may be difficult to read in direct sunlight.

Configurations

A maximum of 4 temperature controllers, including
wired and wireless, can be installed for a water heater
or bank of water heaters. Controllers can only be
wired in parallel. Controllers cannot be wired in
series.
The 4 temperature controllers can consist of multiple
MC-91's or MC-502RC's but only 1 BC-100V and only
1 MC-100V.
Any one of the 5 types of controllers can be installed
by itself and still operate the water heater. All
functions will be available with the exception that the
clock function on the BC-100V will only be available if
an MC-100V is also connected.
If 4 MC-91's are installed, simultaneously press the
Priority and On/Off buttons on the fourth controller
until a beep sounds.
The table to the right shows some of the possible
combinations of controllers.

Cable Lengths and Size

The cable for the temperature controller should be a
non-polarized two-core cable with a minimum gauge
of 22 AWG. The maximum cable length from each
controller to the water heater depends on the total
number of wired controllers connected to the water
heater.
Avoid locations where the temperature controller
could be splashed with liquids.
Do not install in locations where it can be adjusted
by the public.
MC-91
MC-91
MCC-91 + MC-502RC +
MC-91
MC-91
MC-91
Number of Wired
Controllers
VB Series Outdoor LS Manual
Wire controllers in parallel
+
MC-91
+
MCC-91
+
MCC-91
+ MC-502RC
BC-100V
+ MC-502RC +
BC-100V
+
MC-91
+ MC-502RC
+ MC-502RC + MC-502RC
Maximum Cable Length for each
Controller to Water Heater
1
2
3 or 4
Controllers
+
MC-502RC
+
MC-502RC
+
MC-100V
+
MC-100V
+
BC-100V
+
MC-100V
328 ft (100 m)
164 ft (50 m)
65 ft (20 m)
31