Partition Rights; Full Set Rights; None; Partition - Siemens SI120 Configuration Manual

Table of Contents

Advertisement

PIN User
4.7

Partition Rights

O: Forced Set
U: Unset
P: Part Set
M: Reset Alarm
X
(Alarm Memory Re-
set)
T: Buy Time
B: Bypass Time Slot
V: Valid PIN
4.8

Full Set Rights

4.8.1

None

4.8.2

Partition

4.8.3

Room (x)

4.9

Remote Access

16
Siemens Building Technologies
Fire Safety & Security Products
Assign the "partition rights" for each partition.
The user can force the partition to set with inputs (zones) which are not in normal state. If you want to use
this function, you have to define the inputs as bypass able [TM5].
This naturally applies only to inputs which are programmed as bypassable.
The user can switch the partition to unset state.
The user can switch the partition to part set state.
The user can reset the alarm memory.
Normally, the alarm memory has to be reset in order to set the partition.
Exception: setting with automatic resetting of the alarm memory.
The user can extend the time window of the assigned calendar and thus delay the automatic setting. If this
authorization is enabled, the number 9 "Buy time" appears in the user menu authorizations.
The user can block the calendar assigned to the partition from any freely-selectable date/time up to any
freely-selectable date/time.
An Input of the right (valid) PIN activates the Output "Valid PIN" for this Partition
The user is not able to full set the partition.
The user is able to full set the partition.
The user is able to full set only one of the 6 rooms, but not the whole partition.
Allow or deny the user for DTMF control. The User PIN Code allows the access au-
thorization.
If remote access is enabled for user, the user rights for partition set/unset are
IMPORTANT
not taken into consideration. If a user has no right to set a partition locally via
keypad, he can do it by DTMF command.
Procudure to use DTMF Commands:
1.
Call the control unit with the (mobile) phone.
A connection to the control unit is made. This lasts approx. 20 seconds.
2.
Wait until a long buzzer sound is heard.
3.
Enter user PIN.
07.2009