Controller In "Nonoperated State; Safety Concept; Setting Levels And Access Rights - Siemens RVD240 Basic Documentation

District heating and domestic hot water controller
Table of Contents

Advertisement

106/126
Siemens Building Technologies
HVAC Products
Procedure
Keep
depressed and press
Keep
depressed and press

31.1.4 Controller in "nonoperated state"

The controller assumes the "nonoperated state" when, during the last 8 minutes, none
of the buttons has been pressed or, previously, one of the operating mode buttons has
been pressed.
In the "nonoperated state", the time of day and all actual values can be viewed by pres-
sing the setting buttons
those on operating line 161. Any active limitations are indicated by
the priority. They can be retrieved on operating line 169.
When switching on again after a power failure, the display always shows the time of
day. Then, the display selected last will reappear.

31.1.5 Safety concept

The safety concept includes 3 choices aimed at protecting the unit against tampering:
• The functions or settings of function block "Locking functions" are locked on the
software side.
Locking can be overridden (for details, refer to the subsection below)
• With the locking on the hardware side, overriding of locking on the software side can
be prevented (also refer to section 28.3)
• The fixing screws on the controller front are recessed; the holes can be protected
with a sealing label which will be destroyed on removal

31.1.6 Setting levels and access rights

The operating lines are assigned to three different levels. Assignment and access are
as follows:
Level
Operating
lines
End-user
1...50
Heating engineer
51...170
Locking functions
171...196
code
When changing to the next lower setting level, all settings of the higher setting level
remain activated.
Basic documentation RVD240
31 Handling
Effect
Selection of the next higher function block
Selection of the next lower function block
and
. The codes of the actual values are identical with
Access
Press
or
Press
and
operating lines
1. Press
and
2. The display shows Cod 00000
3. The code consists of 5 buttons:
order.
4. Select the operating lines.
Information about the code of OEM versions is
provided by the Siemens sales offices
or
depending on
, then select the operating lines
for 3 seconds, then select the
for 6 seconds
must be pressed in this
CE1P2384en