Error Codes; Restrictions - Panasonic GT02 Manual

Gt series programmable display
Hide thumbs Also See for GT02:
Table of Contents

Advertisement

3.1.7 Error Codes

The error codes are as follows.
Error codes
For GT01, GT11 and GT21
Error code
ER00
BCC error
ER01
Format error
ER02
NOT supported error
ER03
Address error
ER04
Receive buffer overflow
ER05
Requested overflow
ER06
Data error
ER07
Data write inhibit error
For GT02, GT02L, GT05, GT12, GT32 and GT32-E
Error code
**0000
BCC error
**0001
Format error
**0002
NOT supported error
**0003
Address error
**0004
Receive buffer overflow
**0005
Requested overflow
**0006
Data error
**0007
Data write inhibit error
Note) These are the error codes related to communicaiton.

3.1.8 Restrictions

Allowable bytes sent and received
The allowable number of bytes to be sent and received in the GT is up to 512 bytes (including CR).
Therefore, a command or response of which size is more than 513 bytes cannot be sent from the
external device.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Error name
The value of BCC may be incorrect. Check if there is no
calculation mistake.
A command format may be incorrect. Check if it is correct.
A command used is not supported with the version of the
GT. Upgrade the version of the GT, or use another
command.
The address specified does not exist in the GT. Check the
address of the transmitted command.
The sent command exceeds the receivable number of
bytes. Check the number of bytes of the sent command.
The sent readout command exceeds the number of bytes
that can send back. Check the number of the read words.
The communication condition for the GT may be
unmatched with the condition for a destination device.
Check the communication conditions.
A command for the address that writingn is not available
was sent. Check the address of the sent command.
Error name
The value of BCC may be incorrect. Check if there is no
calculation mistake.
A command format may be incorrect. Check if it is correct.
A command used is not supported with the version of the
GT. Upgrade the version of the GT, or use another
command.
The address specified does not exist in the GT. Check the
address of the transmitted command.
The sent command exceeds the receivable number of
bytes. Check the number of bytes of the sent command.
The sent readout command exceeds the number of bytes
that can send back. Check the number of the read words.
The communication condition for the GT may be
unmatched with the condition for a destination device.
Check the communication conditions.
A command for the address that writingn is not available
was sent. Check the address of the sent command.
Measures
Measures

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gt03-eGt05Gt12Gt32Gt32-eGt707 ... Show all

Table of Contents