Setting the NV Communications

Set the NV - CP1E communications as the screen data.
NV-CP1E communications setting example
The CP1E communications was set as follows. Set the same for the NV communications.
Mode:
Baud rate:
Data length:
Stop bit:
Parity bit:
 The stop bit for the NV serial communications is fixed to 1.
Therefore, the stop bit of the PLC serial port must be changed from the default 2 to 1.
Setting the NV communications
1. Select PT – NV Configuration from the menu bar.
2. Select the Communication Parameters Tab. Set the communications with the CP1E.
Click the OK Button to close the dialog box. This completes the NV communication setting.
NV-series PT Simple Operation Handbook
Host Link
115,200 bps
7
1
Even
Click!!
Click!!
Set these items for
communications with the
CP1E.
15