Troubleshooting; Diagnostic Leds - Trane Axiom GEHB 006 Installation, Operation And Maintenance Manual

Horizontal/vertical water-source comfort system
Table of Contents

Advertisement

WARNING
Hazardous Service
Procedures!
The maintenance and trouble
shooting procedures recommended
in this section of the manual could
result in exposure to electrical,
mechanical or other potential safety
hazards. Always refer to the safety
warnings provided throughout this
manual concerning these
procedures. When possible,
disconnect all electrical power
including remote disconnects before
servicing.
Follow proper lockout/tagout
procedures to ensure the power can
not be inadvertently energized.
When necessary to work with live
electrical components, have a
qualified licensed electrician or other
individual who has been trained in
handling live electrical components
per these tasks. Failure to follow all
of the recommended safety
warnings provided, could result in
death or serious injury.
Deluxe Controls
Troubleshooting units which contain
the deluxe control option may be
made easy by using the three LEDs
(light emitting diodes). These LEDs
are provided for indicating the
operating mode of the controller.
The LEDs are intended to aid in
troubleshooting maintenance. The
LEDs are labeled on the circuit board
with numbers as referenced in
Table
8.
92

Troubleshooting

Table 8.

Diagnostic LEDs

Color: Green
Color: Red
LED1
LED2
LED3
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
FLASH
ON
OFF
ON
FLASH
ON
OFF
ON
FLASH
ON
ON
FLASH
FLASH
ON
ON
ON
ON
ON
FLASH
ON
FLASH
OFF
ON
ON
OFF
Controller
Mode
Control OFF
Normal/Compressor OFF
Anti-short cycle
Normal/Compressor ON
Brownout Condition
Soft Lockout (low pressure)
Soft Lockout (high pressure)
Manual Lockout (low pressure)
Manual Lockout (high pressure)
Manual Lockout (condensate overflow)
Compressor Disable
WSHP-SVX01E-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents