Gev 12 1/2 Through 25 Ton Clearance Dimensions - Trane Axiom GEHB 006 Installation, Operation And Maintenance Manual

Horizontal/vertical water-source comfort system
Table of Contents

Advertisement

GEV 1/2 through 5 Ton
Clearance Dimensions
Access to the unit for service
purposes should be provided at
installation. All configurations
require an 24" (610 mm) surround
clearance from other mechanical and
electrical equipment (where shown)
to enable panel removal from the
unit for service/maintenance ability.
Some local codes require a greater
service clearance than listed below.
Check all code requirements prior to
unit installations. Units in a free
return application will require more
than a 1" (25.4) clearance to provide
proper air flow to the units air-to-
refrigerant coil.
GEV 6 through 10 Ton
Clearance Dimensions
Minimum access for service
clearances are provided below. Any
one unit side other than the control
panel or return-air side may be
placed against a wall. The unit may
be serviced through the three
remaining open sides. Some local
codes require a greater service
clearance than listed below. Check all
code requirements prior to unit
installations.
GEV 12 1/2 through 25
Ton Clearance
Dimensions
The diagram below outlines the
minimum required unit service
clearances. Any one unit side other
than the control panel or return-air
side may be placed against a wall.
The unit may be serviced through the
three remaining open sides. Some
local codes require a greater service
clearance than listed below. Check all
code requirements prior to unit
installations.
10
Dimensions
24"
UNIT FRONT
(610)
(25.4)
RIGHT RETURN
TOP/BACK SUPPLY
Figure 5.
GEV 1/2 through 5 ton clearance
ACCESS PANEL FOR
SHEAVES AND BELTS
Figure 6.
GEH 6 through 15 ton clearance
FRONT RETURN-AIR
BACK SUPPLY-AIR
CONTROL BOX
NEC REQ.
MIN. 36" (914)
C.B. TO WALL
CLEARANCE
Figure 7.
GEV 12 1/2 through 25 ton clearance
1"
1"
(25.4)
FRONT RETURN
TOP SUPPLY
20"
(508)
SERVICE
CLEARANCE
18" (457)
UNIT FRONT
16" (406) TO
FILTER FRAME
FOR RETURN-AIR
24"
UNIT FRONT
(610)
LEFT RETURN
TOP/BACK SUPPLY
36"
(914)
SERVICE
CLEARANCE
MIN. SERVICE
CLEARANCE FOR
EITHER LEFT
OR RIGHT SIDE
IS 18" (457). FOR
FAN SHAFT REMOVAL,
A 22" (559) CLEARANCE
MUST BE PROVIDED
ON EITHER THE
LEFT OR RIGHT SIDE.
WSHP-SVX01E-EN