1.3.5 Restrictions on Consumption Current

Including other units, the consumption current should be within the allowable capacity of a
power supply unit.
 Unit's consumption current table (24 V)
CPU Unit
When attaching
Extension Cassette
(Communication
Cassette) to CPU
Unit
(Note 1) (Note 2)
Serial Communication Unit
When attaching
Extension Cassette
(Communication
Cassette) to Serial
Communication Unit
(Note 1) (Note 2)
(Note 1) The consumption currents listed in the Extension Cassette column indicate the increased amount of the
CPU's consumption current which increases when each extension cassette is added.
(Note 2) The consumption current of extension cassette (communication cassette) varies according to the unit to
which the cassette is attached (CPU or serial communication unit).
REFERENCE
For information on the restrictions on the combination of units, also refer to FP7 CPU
Unit User's Manual (Hardware).
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Product name
196k steps, Built-in Ethernet
function
120k steps, Built-in Ethernet
function
120k steps, No Ethernet function
RS-232C x 1ch
RS-232C x 2ch
RS-422 / 485 x 1ch
RS-422 / 485 x 2h
RS-232C x 1ch
RS-422 / 485 x 1ch
Ethernet
RS-232C x 1ch
RS-232C x 2ch
RS-422 / 485 x 1ch
RS-422 / 485 x 2h
RS-232C x 1ch
RS-422 / 485 x 1ch
1.3 Restrictions on Units Combination
Model number
AFP7CPS4E
200 mA or less
AFP7CPS3E
200 mA or less
AFP7CPS3
200 mA or less
AFP7CCS1
35 mA or less
AFP7CCS2
60 mA or less
AFP7CCM1
60 mA or less
AFP7CCM2
90 mA or less
AFP7CCS1M1
70 mA or less
AFP7CCET
35 mA or less
AFP7NSC
50 mA or less
AFP7CCS1
20 mA or less
AFP7CCS2
40 mA or less
AFP7CCM1
30 mA or less
AFP7CCM2
60 mA or less
AFP7CCS1M1
50 mA or less
Consumption
current (mA)