General-Purpose Communication
KEY POINTS
Specify the port targeted for communication, using UNITSEL instruction
immediately before GPSEND instruction.
Maintain the ON conditions for GPSEND instruction until sending is
completed and the general-purpose communication sending active flag (Y8,
Y9, YA, YB) turns OFF.

9.3.2 Contents of Sent Data

Strings data sent by the GPSEND instruction are converted into ASCII text and saved in a
given data register.
 Sent data table
 Once the sent data are converted into strings data using the SSET instruction, the No. of
characters is saved in the header area. The sent data are saved starting with lower bytes of
the subsequent address.
U5
DT100
DT101
H42(B)
H44(D)
DT102
-----
DT103
-----
DT104
KEY POINTS
The start code and the end code specified in the configuration menu are
automatically added to the sent data. Do not include the start code or the
end code into sent data.
The maximum volume of data that can be sent is 4,096 bytes. If the start
code is set to valid, the maximum size is 4,096 bytes including the start
code and the end code.
It is also possible to send binary data.
9-6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
After executing SSET instruction, the No. of characters is set.
H41(A)
Strings of the No. of bytes specified by GPSEND instruction
H43(C)
are sent, in ascending order from lower bytes.
H45(E)
-----