Specifications

Operating voltage
Standby current
Alarm current
RS-485 communications
Data wiring
Remote key switch circuit
Ground fault impedance
Power wiring
Display area
Dimensions (H x W x D)
Mounting
Operating environment
R Series Remote Annunciators and Expander Installation and Operation Guide
24 VDC, continuous. Do not use FACP accessory
power outputs that are interrupted when the panel
is reset. Supply must be UL/ULC Listed for use with
fire protective signaling systems and have a rating
designation of Regulated 24 DC or Regulated 24
FWR.
RLCD, RLCD-R: 98 mA
RLCDF: 98 mA
RLCD-C, RLCD-CR: 99 mA
RLCD-CF: 99 mA
RLED-C, RLED-CR: 28 mA
RLED-CF: 28 mA
RLED24, RLED24R: 6 mA
RLCD, RLCD-R: 113 mA
RLCDF: 113 mA
RLCD-C, RLCD-CR: 115 mA
RLCD-CF: 115 mA
RLED-C, RLED-CR: 62 mA
RLED-CF: 62 mA
RLED24, RLED24R: 34 mA
Class A or Class B, 9600 baud
18 to 14 AWG (1.0 to 2.5 sq mm) twisted pair (6
twists per foot minimum). Maximum wire run is
4,000 ft. (1,219 m)
5 VDC at 1 mA, power-limited, unsupervised
0 Ω
18 to 14 AWG (1.0 to 2.5 sq. mm)
4 lines of 20 characters each
5-5/8 x 8-1/2 x 1-1/2 in. (14.3 x 21.4 x 3.8 cm)
North American 4-inch square electrical box or
listed enclosure (see Error! Not a valid result for
table.)
Temperature: 32 to 120°F (0 to 49°C)
Humidity: 0 to 93% RH, noncondensing at 90°F
(32°C)
Specifications
9